Final | 3/28/2014 | 3/28/2014 | 3/28/2014 | P | PASS |
Rex Boyles
|
|
|
Brent Phone #: ###-#### final ok
|
Final | 3/5/2014 | 3/6/2014 | 3/6/2014 | A | FAIL |
Rex Boyles
|
|
|
brent Phone #: ###-#### NEC 210.8(A)(7) receptacles installed within 6 feet of outside edge of sinks need to be GFI protected. bath and laundry room. NEC 210.12(B) all 120 volt 15 or 20 amp circuits supplying outlets in bedrooms shall be protected by a arc fault circuit interupter device. If someone other than homeowner is performing the electrical work, they need to pull a permit in their name.
|
ELE-Request for Extension | 6/7/2013 | 6/7/2013 | 6/7/2013 | P | PASS |
Rock A. Hudson
|
|
|
brent Phone #: ###-#### Extension ok
|
Electrical Rough-In | 12/28/2012 | 12/31/2012 | 12/31/2012 | P | PASS |
Rock A. Hudson
|
|
|
Brent Phone #: ###-#### basement rough in ok cover
|
Electrical Rough-In | 12/27/2012 | 12/27/2012 | 12/27/2012 | P | FAIL |
Bob Reichert
|
|
|
Brent Phone #: ###-#### shall provide 6" free conductor length in boxes, shall provide 1 1/4" for conductors on studs, shall close openings in water heater j-box
|
Conference | 12/21/2012 | 12/24/2012 | 12/24/2012 | A | DONE |
Rock A. Hudson
|
|
|
brent Phone #: ###-#### Discussed outlet layouts, grounding of metal boxes, removal of old wiring, and future hot tub bonding requirements
|