Final | 7/11/2013 | 7/12/2013 | 7/12/2013 | P | PASS |
Daryl DeGrange
|
|
|
Someone will be there Phone #: ###-#### >> Inspection requested via web by Clay Morgan final ok
|
Final | 1/17/2013 | 1/18/2013 | 1/18/2013 | P | NH |
Daryl DeGrange
|
|
|
Back garage door will be unlocked Phone #: ###-#### >> Inspection requested via web by Clay Morgan Nobody home at time of inspection
|
Final | 1/3/2013 | 1/4/2013 | 1/4/2013 | A | NR |
Daryl DeGrange
|
|
|
The earlier the better so we can get power turned on. If you have any questions, please call Clay. Thank You. Phone #: ###-#### >> Inspection requested via web by Clay Morgan Should of been scheduled for permanent service
|
Permanent Service | 1/4/2013 | 1/4/2013 | 1/4/2013 | P | PASS |
Daryl DeGrange
|
|
|
corrections completed, p/s o/h rec ok
|
Electrical Rough-In | 1/2/2013 | 1/3/2013 | 1/3/2013 | P | FAIL |
Bob Reichert
|
|
|
Let me know if there are any problems and please final if everything is good. Thanks Phone #: ###-#### >> Inspection requested via web by Clay Morgan called, shall add secure support to riser, shall add guy kit if over 3' over roof, shall add ground rods, shall ground incoming water pipe within 5' of entering structure
|