Final | 4/12/2013 | 4/12/2013 | 4/12/2013 | P | PASS |
Bob Reichert
|
|
|
justin Phone #: ###-#### ok final
|
Final | 4/3/2013 | 4/4/2013 | 4/4/2013 | A | FAIL |
Bob Reichert
|
|
|
justin Phone #: ###-#### called contractor, people moving in, could not check all outlets, bath gfci circuits tripping laundry room, receptacles loose, receptacles not projecting from faceplates, jetted tub not gfci protected, energy efficient bulbs not installed, sink does not have gfci installed, panel schedule not completed, sink does not have gfci within 3'
|
Electrical Rough-In | 2/20/2013 | 2/21/2013 | 2/21/2013 | A | PASS |
Bob Reichert
|
|
|
justin Phone #: ###-#### ri ok
|