Temporary Service | 3/13/2013 | 3/14/2013 | 3/14/2013 | A | PASS |
Bob Reichert
|
|
|
Contact: Garrett Collins. Please call before going Phone #: ###-#### >> Inspection requested via web by Deb Gooden corrections made, t/s o/h n ok
|
Temporary Service | 3/11/2013 | 3/12/2013 | 3/12/2013 | P | FAIL |
Bob Reichert
|
|
|
Contact: Garrett Collins, call before going please Phone #: ###-#### >> Inspection requested via web by Deb Gooden called, left correction notice, NEC 210.53(G) grounding electrode shall not be driven at less than 45 degree angle, 408.4 shall provide circuit directory, 400.5(A) #4 soow only rated at 60A, trailer requires min 100A service, 590.6(1) cord outlet requires gfci protection
|