Final | 8/2/2013 | 8/2/2013 | 8/2/2013 | P | PASS |
Bob Reichert
|
|
|
Enrique Phone #: ###-#### ok final
|
Final | 7/11/2013 | 7/11/2013 | 7/11/2013 | P | FAIL |
Daryl DeGrange
|
|
|
Enrique Phone #: ###-#### NEC 210.52(B)(2) Shall have a minimum of two applance circuits serving kitchen counter tops.NEC 406.11 All 15 and 20 ampere receptacles shall be listed tamper resistance in dwelling units. NEC 210.8 Receptacles within 6 ft. of an sink or basin require GFCI protection
|
Electrical Rough-In | 3/26/2013 | 3/26/2013 | 3/26/2013 | P | PASS |
Daryl DeGrange
|
|
|
enrique Phone #: ###-#### - call 30 mins prior r/i ok cover
|
Electrical Rough-In | 3/22/2013 | 3/25/2013 | 3/25/2013 | A | CANC |
Daryl DeGrange
|
|
|
call 1/2 hr ahead to meet//Enrique Phone #: ###-#### --- cancelled per Enrique, will call back to reschedule; I called inspector 3/25/13 leg
|
Electrical Rough-In | 3/19/2013 | 3/20/2013 | 3/20/2013 | A | NR |
Daryl DeGrange
|
|
|
enrique - call 30 mins prior Phone #: ###-#### Not ready
|
Conference | 3/15/2013 | 3/18/2013 | 3/18/2013 | P | DONE |
Daryl DeGrange
|
|
|
Please call 30 min before going out - Enrique Phone #: ###-#### Discussed with homeowner requirements for remodel,removal of nob and tub wiring. Homeowner agreed to remove enough sheetrock to inspect all new wiring.
|