Final | 3/28/2013 | 3/28/2013 | 3/28/2013 | P | PASS |
Daryl DeGrange
|
|
|
final ok
|
Electrical Rough-In | 3/28/2013 | 3/28/2013 | 3/28/2013 | P | PASS |
Daryl DeGrange
|
|
|
Please final this also. Thank you. Phone #: ###-#### >> Inspection requested via web by Clay Morgan corrections done rough-in ok
|
Electrical Rough-In | 3/26/2013 | 3/26/2013 | 3/26/2013 | P | FAIL |
Daryl DeGrange
|
|
|
Installed power to AC and gas furnace in suite A. Someone will be there all day. Please final. Thanks Phone #: ###-#### >> Inspection requested via web by Clay Morgan Over current protection for outdoor unit exceeds maximum, Sealtite flex requires strap, A/C outdoor unit requires service receptacle within 25 ft.
|