Final | 6/18/2013 | 6/19/2013 | 6/19/2013 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov Final ok
|
Final | 6/18/2013 | 6/18/2013 | 6/18/2013 | P | FAIL |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov 30 ampere over current device on A/C unit on 25 ampere max, only two screws out of six in service panel
|
Rough-In Permanent Service | 4/5/2013 | 4/8/2013 | 4/8/2013 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov Rough in ok cover p/s u/g n ok
|
Rough-In Permanent Service | 4/4/2013 | 4/4/2013 | 4/4/2013 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov 210.52- Nook- receptical not located with in 6' of door on right side. 250.96- 3/0 boxes- all metal non current carrying parts shall be bonded. 300.4- bored holes in framing member shall be protected from physical damage by nail plates. Bedroom circuit not complete.
|