Final | 7/15/2013 | 7/15/2013 | 7/15/2013 | P | PASS |
Rock A. Hudson
|
|
|
scott Phone #: ###-#### Final ok
|
Final | 7/11/2013 | 7/12/2013 | 7/12/2013 | P | FAIL |
Rock A. Hudson
|
|
|
Scott-basement & 1st floor Phone #: ###-#### 517.20 All 120 volt recepticals with in 6' of sink or wet care areas shall have GFCI protection. Exam rooms
|
Electrical Rough-In | 7/1/2013 | 7/2/2013 | 7/2/2013 | A | PASS |
Bob Reichert
|
|
|
Ceiling inspection please-Scott-Upstaris office area Phone #: ###-#### ok cover ceilings main floor
|
Electrical Rough-In | 5/21/2013 | 5/22/2013 | 5/22/2013 | A | PASS |
Bob Reichert
|
|
|
cover Phone #: ###-#### as early as possible please. corrections made, ok cover walls only
|
Electrical Rough-In | 5/20/2013 | 5/21/2013 | 5/21/2013 | A | FAIL |
Bob Reichert
|
|
|
insp. to cover Phone #: ###-#### suite 102, called, shall strap mc and flex, shall ground metal boxes, shall use redundant ground mc cable in patient area, shall not strap mc in valley of stud, shall provide mud ring, shall secure emt within 3' of box, fix and recall for ri
|