Final | 7/11/2013 | 7/12/2013 | 7/12/2013 | A | PASS |
Bob Reichert
|
|
|
Call for accesss - steve Phone #: ###-#### corrections made, ok final
|
Final | 7/11/2013 | 7/11/2013 | 7/11/2013 | P | NH |
Bob Reichert
|
|
|
Call for access Phone #: ###-#### >> Inspection requested via web by steve sellers called, left message
|
Final | 6/10/2013 | 6/10/2013 | 6/10/2013 | P | FAIL |
Bob Reichert
|
|
|
Steve Phone #: ###-#### called, shall use tamper resistant receptacles, put on outlet covers, supply 50% energy efficient bulbs, provide ring and blank cover for gec, protect nm cable in garage
|
Rough-In Permanent Service | 5/6/2013 | 5/6/2013 | 5/6/2013 | P | PASS |
Bob Reichert
|
|
|
steve Phone #: ###-#### corrections made, check hose bib below panel at final, ri ok, p/s o/h n ok
|
Permanent Service | 4/29/2013 | 4/29/2013 | 4/29/2013 | P | FAIL |
Bob Reichert
|
|
|
steve Phone #: ###-#### called, shall provide work pace about equipment (pipes front of service), shall provide schedule 80 pvc out of bottom of panel, label breakers, clean meter socket up
|