Final | 3/26/2018 | 3/27/2018 | 3/27/2018 | P | PASS |
Rock A. Hudson
|
|
|
Please contact John Mittleider for questions regarding inspection details. Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek Final ok
|
ELE-Aging Inspection | 1/11/2018 | 1/11/2018 | 1/11/2018 | | PASS |
Rock A. Hudson
|
|
|
Still under construction
|
Electrical Rough-In | 10/12/2017 | 10/13/2017 | 10/13/2017 | A | PASS |
Rock A. Hudson
|
|
|
Call John for fountain bonding on site. Phone #: ###-#### Inspection requested via web by Tom Betty Perimeter walls bonding rough in ok cover
|
Electrical Rough-In | 9/19/2017 | 9/20/2017 | 9/20/2017 | P | PASS |
Rock A. Hudson
|
|
|
Call John for fountain bonding. Phone #: ###-#### Inspection requested via web by Tom Betty Provisions provided for bonding perimeter benches, water line just past drains. Conduits under this area are for low voltage lighting associated with pool. All metal associated with pour bonded, drains, caps, rebar. Perimeter walls to be opened up to expose rebar for bonding and equipment will be in basement under silo to west. Bonding rough in ok cover
|
Electrical Rough-In | 9/19/2017 | 9/19/2017 | 9/19/2017 | P | NR |
Rock A. Hudson
|
|
|
Contact John for bonding of fountain on site. Phone #: ###-#### Inspection requested via web by Tom Betty Requested for wrong day installation not complete. Will recall
|
Electrical Rough-In | 9/12/2017 | 9/12/2017 | 9/12/2017 | P | PASS |
Rock A. Hudson
|
|
|
Contact John to inspect light pole base on southwest corner of site park. Phone #: ###-#### Inspection requested via web by Tom Betty Rough in ok cover
|
Electrical Rough-In | 8/17/2017 | 8/21/2017 | 8/22/2017 | A | FAIL |
Rock A. Hudson
|
|
|
Contact John for heat trace rough in and talk bonding at water feature on park site. Phone #: ###-#### Inspection requested via web by Tom Betty Discussed requirements for new water feature between Annex and HQ. If standing water and public has access to wade in water pool requirements of article 680 apply. Contact stated this body of water is to have public access for wading. All Code requirements for a pool apply. 680.11- Underground is wiring is not permitted under a pool unless this wiring is necessary to supply pool equipment. 680.26(A)- The equipotential bonding required by 680.26 shall be installed to reduce voltage gradients in the pool area including 3 existing perimenter walls. 680.27(C)(3)- Radiant heating cables are not permitted under or in pool deck.
|
Electrical Rough-In | 8/2/2017 | 8/3/2017 | 8/3/2017 | A | PASS |
Rock A. Hudson
|
|
|
Call john for underground raceways on site. Phone #: ###-#### Inspection requested via web by Tom Betty Tractor pad S.W. corner and additional length towards S.W. corner not yet to final location rough in ok cover
|
Final | 7/28/2017 | 7/31/2017 | 7/31/2017 | A | FAIL |
Rock A. Hudson
|
|
|
Walk down fountain controls and spiral slide on exterior of building. Phone #: ###-#### Inspection requested via web by Tom Betty 110.3- Shall verify listing of spiral slide and components. Found listing for control cabinet, verify if all are part of same listing. 680.26(B)(2)- Although water feature does not meet the definition of a pool, AHJ shall require bonding of perimeter surfaces and equipment associated due to wet concrete in area of foggers. If accessible #8 solid continue to equipment from shells as inspected in June of 2016 and shall include electrical equipment discribed in 680.26(B)(6). 400.17- Power supply cord entering control cabinet shall be protected from physical damage where it enters or be relocated to interior.
|
Final | 7/20/2017 | 7/20/2017 | 7/20/2017 | P | PART |
Rock A. Hudson
|
|
|
Contact Tony Keen for sign off of level 5 deck JUMP structure. No final for JUMP site/park. Phone #: ###-#### Inspection requested via web by Tom Betty Parking garage slides and sight mister fountain listings need confirmed. Central area and several tractor boxes with power and lighting yet to be built. Level 5 play area, BBQ area TCO ok
|
Electrical Rough-In | 5/22/2017 | 5/23/2017 | 5/23/2017 | P | PASS |
Rock A. Hudson
|
|
|
Please inspect the next site amphitheater wall rough in raceways and boxes. Phone #: ###-#### Inspection requested via web by Tom Betty Level 7 pour rough in ok cover
|
Electrical Rough-In | 5/12/2017 | 5/15/2017 | 5/15/2017 | P | PASS |
Rock A. Hudson
|
|
|
Please inspect pvc in wall #6 of the amphitheater. Phone #: ###-#### Inspection requested via web by Tom Betty Area noted rough in ok cover
|
Electrical Rough-In | 5/5/2017 | 5/8/2017 | 5/8/2017 | A | PASS |
Rock A. Hudson
|
|
|
Please inspect amphitheater wall #5. Please walk with Tony to sign off hard card on Simplot Headquarters past inspection. Phone #: ###-#### Inspection requested via web by Tom Betty Unable to sign on vanilla space under BLD16-03847. A seperate electrical permit required. Level 5 of ampitheater rough in ok cover.
|
Electrical Rough-In | 4/28/2017 | 4/28/2017 | 4/28/2017 | P | PASS |
Rock A. Hudson
|
|
|
Rough in inspection on amphitheater wall #4 only at JUMP site. Contact Tony Keen if escort is needed. Phone #: ###-#### Inspection requested via web by Tom Betty Level 4 pour amphitheater rough in ok cover
|
Electrical Rough-In | 4/20/2017 | 4/20/2017 | 4/20/2017 | A | PASS |
Rock A. Hudson
|
|
|
Call Tony Keen for concrete wall rough in at amphitheater in park area. Phone #: ###-#### Inspection requested via web by Tom Betty Level 3 of sitting area, tractor pad and planter underground to south of HQ rough in ok cover
|
Electrical Rough-In | 4/13/2017 | 4/14/2017 | 4/14/2017 | P | PASS |
Rock A. Hudson
|
|
|
Call Tony Keen for rough in concrete pour on site. Phone #: ###-#### Inspection requested via web by Tom Betty Sitting area of ampatheater level 2 wall pour rough in ok cover
|
ELE-Aging Inspection | 3/16/2017 | 3/16/2017 | 3/16/2017 | | PASS |
Rock A. Hudson
|
|
|
Still under construction
|
Electrical Rough-In | 12/14/2016 | 12/14/2016 | 12/14/2016 | P | PASS |
Rock A. Hudson
|
|
|
site underground. call Frank Phone #: ###-#### Inspection requested via web by Brandon Robinson Underground south stack 4 and ampatheater wall rough in ok cover
|
Electrical Rough-In | 11/3/2016 | 11/3/2016 | 11/3/2016 | P | PASS |
Rock A. Hudson
|
|
|
underground site. call Frank Phone #: ###-#### Inspection requested via web by Brandon Robinson HQ south columns stack 1 column lights rough in ok cover
|
Electrical Rough-In | 10/31/2016 | 11/1/2016 | 11/1/2016 | A | PASS |
Rock A. Hudson
|
|
|
site underground. call Frank Phone #: ###-#### Inspection requested via web by Brandon Robinson South area west of tractors to narrow section underground rough in ok cover
|
Electrical Rough-In | 10/24/2016 | 10/25/2016 | 10/25/2016 | A | PASS |
Rock A. Hudson
|
|
|
site underground. Call Frank Phone #: ###-#### Inspection requested via web by Brandon Robinson Small area to S.W. of tractors in ampatheater area underground rough in ok cover
|
Electrical Rough-In | 10/21/2016 | 10/21/2016 | 10/21/2016 | P | PASS |
Rock A. Hudson
|
|
|
site underground. call Frank Phone #: ###-#### Inspection requested via web by Brandon Robinson Area to west of tractors in ampatheater underground rough in ok cover
|
Electrical Rough-In | 10/17/2016 | 10/17/2016 | 10/17/2016 | P | PASS |
Rock A. Hudson
|
|
|
underground site. call Frank Phone #: ###-#### Inspection requested via web by Brandon Robinson Discussed progress on south egress lighting for stair 1. I was informed site crew not providing egress lighting. Asked site crew meet with building electrical foreman and double check who is providing lighting for egress as it is required. Partial underground south side west of tractors rough in ok cover.
|
Electrical Rough-In | 10/14/2016 | 10/14/2016 | 10/14/2016 | P | CANC |
Rock A. Hudson
|
|
|
underground site. call Frank Phone #: ###-#### >> Inspection requested via web by Brandon Robinson Inspection cancelled from web by: Brandon Robinson
|
Electrical Rough-In | 10/10/2016 | 10/11/2016 | 10/11/2016 | A | PASS |
Rock A. Hudson
|
|
|
site underground inspection. call Frank Phone #: ###-#### Inspection requested via web by Brandon Robinson Water feature area to be future inspection. Area south of Annex breezeway underground rough in ok cover
|
Electrical Rough-In | 10/7/2016 | 10/7/2016 | 10/7/2016 | P | PASS |
Daryl DeGrange
|
|
|
underground inspection on site. Call Frank Phone #: ###-#### Inspection requested via web by Brandon Robinson Rough-in ok cover 3 pole bases stack area 4 level 1 east exit
|
Electrical Rough-In | 9/29/2016 | 9/29/2016 | 9/29/2016 | A | PASS |
Rock A. Hudson
|
|
|
site underground. Call Frank Phone #: ###-#### Inspection requested via web by Brandon Robinson Area between HQ and Annex underground and south pole bases rough in ok cover
|
Electrical Rough-In | 9/28/2016 | 9/28/2016 | 9/28/2016 | P | PASS |
Rock A. Hudson
|
|
|
underground between HQ building and Annex building. Call Frank Phone #: ###-#### Inspection requested via web by Brandon Robinson South side of HQ and east 1/2 off annex underground rough in ok cover.
|
Conference | 9/19/2016 | 9/20/2016 | 9/20/2016 | A | DONE |
Rock A. Hudson
|
|
|
Tony ###-####. Flag pole bases. Contractor investigated base construction and rebar of flag pole base connected to building rebar system. Additional electrode not required as complete area installed above water membrane so true earth not available by installation of ground rods. Installation as is is sufficient.
|
Conference | 9/19/2016 | 9/19/2016 | 9/19/2016 | P | DONE |
Rock A. Hudson
|
|
|
Contact Tony about flag pole lightning protection. Phone #: ###-#### Inspection requested via web by Tom Betty Discussed the design of base for flag poles which had a 24" electrode to be installed at bottom of flag pole base. At bottom of base, 5' depth, roof of lower parking garage structure is present so installers decided to remove 24" electrode and install it on side of flag pole base. Will discuss with chief electrical and building and will ote 9-20-16.
|
Electrical Rough-In | 9/9/2016 | 9/12/2016 | 9/12/2016 | A | PASS |
Rock A. Hudson
|
|
|
underground south of Annex. call Frank Phone #: ###-#### Inspection requested via web by Brandon Robinson one pole base not ready area noted ok to cover. 3 north flag pole ground rods verify length and specs
|
Electrical Rough-In | 8/27/2016 | 8/29/2016 | 8/29/2016 | P | PASS |
Rock A. Hudson
|
|
|
Northwest corner site underground. Call Frank Phone #: ###-#### Inspection requested via web by Brandon Robinson Area noted rough in ok cover
|
Electrical Rough-In | 8/26/2016 | 8/26/2016 | 8/26/2016 | P | NR |
Rock A. Hudson
|
|
|
site underground northwest corner. call Frank. Phone #: ###-#### Inspection requested via web by Brandon Robinson Will recall
|
Electrical Rough-In | 6/29/2016 | 6/29/2016 | 6/29/2016 | P | PASS |
Rock A. Hudson
|
|
|
underground event lawn. Call Frank Phone #: ###-#### Inspection requested via web by Brandon Robinson West of event lawn area underground rough in ok cover
|
Electrical Rough-In | 6/22/2016 | 6/23/2016 | 6/23/2016 | A | PASS |
Rock A. Hudson
|
|
|
event lawn underground rough in. call Frank Phone #: ###-#### Inspection requested via web by Brandon Robinson Underground north and west of ELE room rough in ok cover. Duplicate request
|
Electrical Rough-In | 6/22/2016 | 6/23/2016 | 6/23/2016 | A | PASS |
Rock A. Hudson
|
|
|
event lawn underground rough in. call Frank Phone #: ###-#### Inspection requested via web by Brandon Robinson Underground north and west of ELE room rough in ok cover
|
Electrical Rough-In | 6/21/2016 | 6/21/2016 | 6/21/2016 | P | PASS |
Rock A. Hudson
|
|
|
event lawn underground inspection on site. call Frank Phone #: ###-#### Inspection requested via web by Brandon Robinson South central from electrical room underground rough in ok cover
|
Electrical Rough-In | 6/17/2016 | 6/17/2016 | 6/17/2016 | P | PASS |
Rock A. Hudson
|
|
|
underground inspection in event lawn. call Frank Phone #: ###-#### Inspection requested via web by Brandon Robinson Underground north and east corners rough in ok cover
|
Electrical Rough-In | 6/3/2016 | 6/6/2016 | 6/6/2016 | P | PASS |
Rock A. Hudson
|
|
|
underground pole light inspection on front street and 9th. Call Frank Phone #: ###-#### Inspection requested via web by Brandon Robinson 6 pole bases north side from 9th to 11th rough in ok cover
|
Electrical Rough-In | 6/1/2016 | 6/2/2016 | 6/2/2016 | A | PASS |
Rock A. Hudson
|
|
|
electrical rough in inspection for event lawn underground near corner of 9th and front . Call Frank Phone #: ###-#### Inspection requested via web by Brandon Robinson South portion of event lawn underground rough in ok cover
|
Electrical Rough-In | 6/1/2016 | 6/1/2016 | 6/1/2016 | P | PASS |
Rock A. Hudson
|
|
|
Contact Brandon for water fountain bonding. Phone #: ###-#### Inspection requested via web by Tony Keen Large fountain perimeter bond rough in ok cover
|
Electrical Rough-In | 5/31/2016 | 6/1/2016 | 6/1/2016 | A | PASS |
Rock A. Hudson
|
|
|
inspection on water feature bonding Phone #: ###-#### Inspection requested via web by Brandon Robinson 2 smaller fountains perimeter bonds rough in ok cover
|
Conference | 5/27/2016 | 5/27/2016 | 5/27/2016 | A | DONE |
Rock A. Hudson
|
|
|
requesting a consultation for JUMP site water feature bonding. Phone #: ###-#### Inspection requested via web by Brandon Robinson Discussed bonding of area around fountain and foggers. Bonds required on rebar on each perimeter area to equipment and GFCI protection
|
Electrical Rough-In | 5/24/2016 | 5/25/2016 | 5/25/2016 | A | PASS |
Rock A. Hudson
|
|
|
underground site work inspection near 9th St. Call Frank at number above. Phone #: ###-#### Inspection requested via web by Brandon Robinson Underground N. E. of drains in vent lawn area rough in ok cover
|
Electrical Rough-In | 5/23/2016 | 5/23/2016 | 5/23/2016 | P | PASS |
Rock A. Hudson
|
|
|
Light pole bases in the park area. Phone #: ###-#### Inspection requested via web by Tony Keen 6 additional small pole bases in park area rough in ok cover
|
Electrical Rough-In | 5/18/2016 | 5/19/2016 | 5/19/2016 | P | PASS |
Rock A. Hudson
|
|
|
Rough in for northeast site underground. Contact Frank Yantis Phone #: ###-#### Inspection requested via web by Tony Keen N.W. corner planter and sidewalk underground rough in ok cover
|
Electrical Rough-In | 5/12/2016 | 5/12/2016 | 5/12/2016 | P | PASS |
Rex Boyles
|
|
|
Contact Frank Yantis for pole base inspection as early as possible. Thanks Phone #: ###-#### Inspection requested via web by Tony Keen r/i ok n. east "event lawn" (4) square pole bases and north side of annex bldg. exterior door control u. slab conduits 2-3/4"
|
ELE-Aging Inspection | 5/6/2016 | 5/6/2016 | 5/6/2016 | | DONE |
Rex Boyles
|
|
|
still under construction
|
Electrical Rough-In | 2/5/2016 | 2/5/2016 | 2/5/2016 | P | CANC |
Rock A. Hudson
|
|
|
Contact Frank Yantis to inspect Boise city street lighting pedestal. Phone #: ###-#### Inspection requested via web by Tom Betty Needed permenant service inspection
|
Permanent Service | 2/5/2016 | 2/5/2016 | 2/5/2016 | P | PASS |
Rock A. Hudson
|
|
|
Contact Frank Yantis to inspect Boise city street lighting pedestal. Phone #: ###-#### Inspection requested via web by Tom Betty Confirmed lighting pedistal inspection. Tagged from 1-13-16 inspection by Rex Boyles. 2 meters required. p/s u/g n ok
|
Conference | 2/2/2016 | 2/2/2016 | 2/2/2016 | P | DONE |
Rex Boyles
|
|
|
Meet Frank Yantis by the large spiral slide on grade level for conference. Phone #: ###-#### Inspection requested via web by Tom Betty Discuss conduits feeding slide power and controls. OK to change to rigid conduit since elevation in depth changed
|
Electrical Rough-In | 1/13/2016 | 1/13/2016 | 1/13/2016 | A | CANC |
Rex Boyles
|
|
|
Call Frank Yantsi for street lighting inspection. Phone #: ###-#### Inspection requested via web by Tom Betty needed p/s
|
Permanent Service | 1/13/2016 | 1/13/2016 | 1/13/2016 | P | PASS |
Rex Boyles
|
|
|
Call Frank Yantsi for street lighting inspection. Phone #: ###-#### Inspection requested via web by Tom Betty street light and xmas light receptacle public works pedestal needs 2 meters p/s u/g n ok
|
Electrical Rough-In | 1/6/2016 | 1/7/2016 | 1/7/2016 | A | PASS |
Rex Boyles
|
|
|
Call Brandon to inspect all JUMP elect. rooms levels 1,2,3,4,5,6 for completness. Phone #: ###-#### Inspection requested via web by Tom Betty Final ok on all electrical rooms. Still need final inspections on unfinished party decks and marketplace areas, Slide electrical and Pioneer Path electrical not completed, all electric signs "by others" and parking control pedestal electrical wiring "by others" before "FINAL" inspection on whole Jump project.
|
Electrical Rough-In | 11/18/2015 | 11/18/2015 | 11/18/2015 | P | PASS |
Rex Boyles
|
|
|
Contact Frank for site work underground. Phone #: ###-#### Inspection requested via web by Tom Betty r/i continue slab on slab ground level conduits ( rock climbing area) ok
|
Electrical Rough-In | 11/13/2015 | 11/16/2015 | 11/16/2015 | A | PASS |
Rex Boyles
|
|
|
Call Frank Yantis for site inspection. Phone #: ###-#### Inspection requested via web by Tom Betty r/i ok slab on slab west of main electrical room level 1
|
Electrical Rough-In | 11/5/2015 | 11/5/2015 | 11/5/2015 | P | PASS |
Rex Boyles
|
|
|
Please contact Frank Yantis. for underground site rough in. Phone #: ###-#### Inspection requested via web by Tom Betty r/i 5 seating planters u.ground conduits ok to cover
|
Electrical Rough-In | 11/3/2015 | 11/4/2015 | 11/4/2015 | A | PASS |
Rex Boyles
|
|
|
Contact brandon for grade level site underground. Phone #: ###-#### Inspection requested via web by Tom Betty pole bases west r/i ok
|
Electrical Rough-In | 10/29/2015 | 10/30/2015 | 10/30/2015 | P | PASS |
Rex Boyles
|
|
|
Contact Frank Yantis for underground rough in on site. Phone #: ###-#### Inspection requested via web by Tom Betty r/i ok slab on slab west and north of water feature ok
|
Electrical Rough-In | 10/29/2015 | 10/29/2015 | 10/30/2015 | P | CANC |
Rex Boyles
|
|
|
Contact Frank Yantis for site underground rough in. Phone #: ###-#### Inspection requested via web by Tom Betty called in wrong date
|
Electrical Rough-In | 10/28/2015 | 10/29/2015 | 10/29/2015 | A | PASS |
Rex Boyles
|
|
|
Contact Frank Yantis for underground raceways on site. Phone #: ###-#### Inspection requested via web by Tom Betty underslab conduits ok at east of main electrical rm. and north of kitchen in helix r/i ok
|
Electrical Rough-In | 10/22/2015 | 10/22/2015 | 10/22/2015 | P | PASS |
Rex Boyles
|
|
|
Contact Frank Yantis for underslab raceways Phone #: ###-#### Inspection requested via web by Tom Betty r/i ok slab on slab parking garage area west of helix only 100%
|
Electrical Rough-In | 9/23/2015 | 9/24/2015 | 9/24/2015 | A | PASS |
Rex Boyles
|
|
|
Contact Frank Yantis for site rough in underground. Phone #: ###-#### Inspection requested via web by Tom Betty r/i ok u.ground for street lights 9th and myrtle
|
Electrical Rough-In | 9/14/2015 | 9/15/2015 | 9/15/2015 | A | PASS |
Rex Boyles
|
|
|
Contact Frank Yantis for underground rough in on grade level site. Phone #: ###-#### Inspection requested via web by Tom Betty r/i ok slab on slab marketplace east
|
Electrical Rough-In | 8/31/2015 | 8/31/2015 | 8/31/2015 | A | PASS |
Rex Boyles
|
|
|
Contact Brandon Robinson to review and sign temporary occupancy. Phone #: ###-#### Inspection requested via web by Tom Betty temporary occupancy ok 1st floor parking garage barricaded area ONLY up to 6th floor. Zach with Hoffman states they will barricade all areas at Myrtle Street entrance area still under construction prior to "temp. occup. ok" with Fire and Building inspectors
|
Final | 8/6/2015 | 8/11/2015 | 8/11/2015 | A | PART |
Rex Boyles
|
|
|
Contact Brandon Robinson for level 4 JUMP inspection Phone #: ###-#### Inspection requested via web by Tom Betty level 4 exterior final ok
|
Electrical Rough-In | 8/7/2015 | 8/7/2015 | 8/7/2015 | P | PASS |
Rex Boyles
|
|
|
Contact Frank Yantis for underground raceways. Phone #: ###-#### Inspection requested via web by Tom Betty 2- 2" raceways feeding street lights on myrtle ok to cover
|
Electrical Rough-In | 7/29/2015 | 7/30/2015 | 7/30/2015 | P | PASS |
Rex Boyles
|
|
|
PLease contact Frank Yantis for a 1:00 p.m. inspection of light poles on 9th and Myrtle sts. Phone #: ###-#### Inspection requested via web by Tom Betty r/i ok 2 light pole bases on 9th street and u. ground conduits
|
Electrical Rough-In | 7/29/2015 | 7/29/2015 | 7/29/2015 | P | CANC |
Rex Boyles
|
|
|
Contact Frank Yantis for pole base rough in on Myrtle and 9th st. as close to 3:00 p.m. as possible please. Phone #: ###-#### Inspection requested via web by Tom Betty Tony called and cancelled this inspection
|
Final | 7/27/2015 | 7/27/2015 | 7/27/2015 | P | PART |
Rex Boyles
|
|
|
Contact Brandon Robinson for level 1 helix final inspection. Phone #: ###-#### Inspection requested via web by Tom Betty r/i slab on slab north of helix ground lights and slab on slab u.ground at helix ramp
|
Final | 7/23/2015 | 7/23/2015 | 7/23/2015 | P | PART |
Rex Boyles
|
|
|
Contact Brandon Robinson for level 3 parking garage final inspection. Phone #: ###-#### Inspection requested via web by Tom Betty level 3 parking garage final ok ALSO r/i ok level 1 underground slab on slab north of helix
|
Electrical Rough-In | 7/17/2015 | 7/17/2015 | 7/17/2015 | P | PASS |
Rex Boyles
|
|
|
Contact Frank Yantis for level 1 underground and level 4 final. Phone #: ###-#### Inspection requested via web by Tom Betty 2 INSPECTIONS; r/i ok 1st floor slab on slab conduits from garage north to kitchen area. FINAL OK 4th flr interior of helix
|
Final | 7/13/2015 | 7/16/2015 | 7/16/2015 | A | PART |
Rex Boyles
|
|
|
PLease contact Brandon Robinson for level 6 ; 7 inspection. Phone #: ###-#### Inspection requested via web by Tom Betty final ok corrections made for 1st floor kitchen island and lockoffs on hand dryers and GFCI protection on drinking fountains and all 120 volt receptacles , 2nd floor sound wall in office, 6th floor 100% and all rooftop on 7 and 8. All exterior GFCI's are now W.R. and ok
|
Final | 7/13/2015 | 7/15/2015 | 7/15/2015 | A | PART |
Rex Boyles
|
|
|
PLease contact Brandon Robinson for level 5 inspection. Phone #: ###-#### Inspection requested via web by Tom Betty level 5 helix final ok EXCEPT exterior planters, slide and party zone area not ready. ALSO r/i ok for Portal walls and soffit sconces
|
Electrical Rough-In | 7/13/2015 | 7/13/2015 | 7/13/2015 | P | PASS |
Rex Boyles
|
|
|
Contact Frank Yantis for undergfround roughin. Phone #: ###-#### Inspection requested via web by Tom Betty r/i u.ground (FOAM) continuation from southwest elevator, south of helix only , west to stiarwell. ok to cover.
|
Final | 7/2/2015 | 7/9/2015 | 7/9/2015 | A | PART |
Rex Boyles
|
|
|
Contact Brandon Robinson for room by room final inspections starting on level 3. Phone #: ###-#### Inspection requested via web by Tom Betty final ok on level3 helix and garden studio including electrical rooms, center of helix large room
|
Final | 7/2/2015 | 7/8/2015 | 7/8/2015 | A | PART |
Rex Boyles
|
|
|
Contact Brandon Robinson for room by room final inspections starting on level 2. Phone #: ###-#### Inspection requested via web by Tom Betty 1st floor helix area partial final ok except kitchen island. 2nd floor helix area partial final ok except conference room sound wall. Checked listings on all light fixtures in these areas also ok. 2nd floor electrical/chiller room final ok
|
Final | 7/2/2015 | 7/7/2015 | 7/7/2015 | A | FAIL |
Rex Boyles
|
|
|
Contact Brandon Robinson for room by room final inspections starting on level 1. Phone #: ###-#### Inspection requested via web by Tom Betty 422.31 and 422.32-disconnect and lockoff required for hand dryers, 210.8(B)-GFCI protection required in other than dwellings kitchens for all 125 volt 20amp receptacles, 422.52-all drinking fountains shall have GFCI protection. 406.8(B)-all receptacles in wet locations shall be listed "weather resistant" type. Please have listings for lumiaires available for inspections.
|
Electrical Rough-In | 7/1/2015 | 7/2/2015 | 7/2/2015 | A | PASS |
Rex Boyles
|
|
|
Contact Frank Yantis for grade level underground raceway inspection. Phone #: ###-#### Inspection requested via web by Tom Betty r/i slab on deck 1st flr south of helix west up to elevator column line ok to cover
|
Electrical Rough-In | 6/19/2015 | 6/22/2015 | 6/22/2015 | A | PASS |
Rex Boyles
|
|
|
Under Slab inspection for JUMP Site work- Contact Frank Yantis for access. Phone #: ###-#### Inspection requested via web by Tom Betty r/i ok slab on grade in parking garage (foam) conduits ok to cover from col.line 9.8 to the east
|
Electrical Rough-In | 6/2/2015 | 6/4/2015 | 6/4/2015 | P | PASS |
Rex Boyles
|
|
|
Contact Brandon Robinson for east side of level 1 site lighting underground. Phone #: ###-#### Inspection requested via web by Tom Betty r/i ok marketplace area A and H underground conduits under foam.
|
Conference | 5/27/2015 | 5/27/2015 | 5/27/2015 | P | DONE |
Rex Boyles
|
|
|
Please come to the JUMP trailer to contact Tony Keen about the fire pump controller. Phone #: ###-#### Inspection requested via web by Tom Betty discuss fire pump controller for helx part of bldg. OK to use 400amp rated controller as per meeting with Jeff and Tony
|
Electrical Rough-In | 5/20/2015 | 5/22/2015 | 5/26/2015 | P | PASS |
Rex Boyles
|
|
|
Contact Brandon Robinson for level 6 kitchen ceiling inspection. Phone #: ###-#### Inspection requested via web by Tom Betty r/i ceiling ok
|
Electrical Rough-In | 5/14/2015 | 5/15/2015 | 5/15/2015 | P | PASS |
Rex Boyles
|
|
|
Contact Dennis Kienitz for above ceiling rough in for level 2. Phone #: ###-#### Inspection requested via web by Tom Betty r/i ok 2nd flr offices and breakroom ceilings, 3rd flr passenger elevator ceiling, 5th flr west fun zone underslab conduits and 1st flr east side "area1" underslab conduits ok
|
Electrical Rough-In | 5/15/2015 | 5/15/2015 | 5/15/2015 | A | NR |
Daryl DeGrange
|
|
|
Contact Brandon Robinson for level 5 in slab rough in. Phone #: ###-#### Inspection requested via web by Tom Betty Not ready at this time.
|
Electrical Rough-In | 5/12/2015 | 5/13/2015 | 5/13/2015 | A | PASS |
Rex Boyles
|
|
|
Call Brandon Robinson for level 6 ceiling rough in. Phone #: ###-#### Inspection requested via web by Tom Betty r/i ok ballroom ceiling 6th flr
|
Conference | 5/12/2015 | 5/12/2015 | 5/12/2015 | P | DONE |
Daryl DeGrange
|
|
|
Contact Toby Davis for conference on light fixture modification. Phone #: ###-#### Inspection requested via web by Tom Betty Discussed with contractor ok relocate junction boxes for LED luminaires
|
Conference | 5/5/2015 | 5/6/2015 | 5/6/2015 | A | DONE |
Daryl DeGrange
|
|
|
Contact Tony Keen in job trailer for Fire Pump Controller consultation. Phone #: ###-#### Inspection requested via web by Tom Betty Discussed fire pump controller provides short circuit protection only as per 695.5(C)(2) requirement. Waiting for Eaton`s electrical engineer (Rick Dottson) to sign off that MCP will operate indefinitely under locked rotor conditions.
|
Electrical Rough-In | 4/29/2015 | 4/29/2015 | 4/29/2015 | P | PASS |
Daryl DeGrange
|
|
|
Call Jon Novak for level 1 rough in. Phone #: ###-#### Inspection requested via web by Tom Betty rough-in ok cover Multi-media rooms ceiling grid
|
Electrical Rough-In | 4/27/2015 | 4/28/2015 | 4/28/2015 | A | PASS |
Daryl DeGrange
|
|
|
Contact Brandon Robinson for level 6 north stairtower AO1& soffit rough in. Phone #: ###-#### Inspection requested via web by Tom Betty rough-in ok cover
|
Electrical Rough-In | 4/23/2015 | 4/24/2015 | 4/24/2015 | A | PASS |
Rex Boyles
|
|
|
Contact Jon Novak for grade level underground installation. Phone #: ###-#### Inspection requested via web by Tom Betty r/i ok under slab power and telco conduits 1st floor east end
|
Electrical Rough-In | 4/21/2015 | 4/22/2015 | 4/22/2015 | A | PASS |
Rex Boyles
|
|
|
Contact Brandon Robinson for level 5 rough in. Phone #: ###-#### Inspection requested via web by Tom Betty r/i party deck "PT deck" conduits ok to cover.
|
Conference | 4/9/2015 | 4/10/2015 | 4/10/2015 | A | DONE |
Rex Boyles
|
|
|
Contact Tony Keen for conference about Fire Pump Controller sizing. Phone #: ###-#### Inspection requested via web by Tom Betty discuss fire pump controller size "400 amp" being to small for locked rotor @ 908 amps. Will get back to them with an answer asap!
|
Electrical Rough-In | 4/8/2015 | 4/8/2015 | 4/8/2015 | P | PASS |
Rex Boyles
|
|
|
Brandon Phone #: ###-#### r/i ok level3 west tractor box walls and ceiling
|
Electrical Rough-In | 3/19/2015 | 3/20/2015 | 3/20/2015 | A | PASS |
Rex Boyles
|
|
|
Contact Brandon Robinson for 4th level east side rough in. Phone #: ###-#### Inspection requested via web by Tom Betty r/i 4th level est side tractor box ceiling and walls ok
|
Final | 3/2/2015 | 3/3/2015 | 3/3/2015 | P | CANC |
Rex Boyles
|
|
|
Contact Brandon Robinson for levels 3,4,and 5 rough in Phone #: ###-#### Inspection requested via web by Tom Betty needed r/i insp.
|
Electrical Rough-In | 3/3/2015 | 3/3/2015 | 3/3/2015 | P | PASS |
Rex Boyles
|
|
|
Contact Brandon Robinson for levels 3,4,and 5 rough in Phone #: ###-#### Inspection requested via web by Tom Betty R/I ceiings ok tractor boxes on level 2,3 and 4. Service elevator lobby ceilings on level 3, 4, 5 and 6 r/i ok
|
Electrical Rough-In | 3/2/2015 | 3/2/2015 | 3/2/2015 | P | CANC |
Rex Boyles
|
|
|
Contact Brandon Robinson for levels 3.4 and 5 roughin. Phone #: ###-#### >> Inspection requested via web by Tom Betty Inspection cancelled from web by: Tom Betty
|
Conference | 2/24/2015 | 2/25/2015 | 2/25/2015 | A | DONE |
Rex Boyles
|
|
|
Contact Toby Davis question on mounting busway sideways on level 6. Phone #: ###-#### Inspection requested via web by Tom Betty discuss receptacles facing up in light box for "Jump room" theatrical room. Ok to face up with "in use covers only".
|
Electrical Rough-In | 2/11/2015 | 2/12/2015 | 2/12/2015 | A | PASS |
Rex Boyles
|
|
|
Cantact Brandon Robinson for level 4 ceiling inspection. Phone #: ###-#### Inspection requested via web by Tom Betty r/i ok level 4 elevator lobby ceiling
|
Electrical Rough-In | 2/9/2015 | 2/10/2015 | 2/10/2015 | P | PASS |
Rex Boyles
|
|
|
Contact Brondon Robinson for upper level ceiling inspection. Phone #: ###-#### Inspection requested via web by Tom Betty r/i ok level 5 ceilings in movement and multi media. Also level 6 overflow lobby ceilings ok
|
Electrical Rough-In | 1/29/2015 | 1/30/2015 | 1/30/2015 | A | PASS |
Rex Boyles
|
|
|
Contact Brandon Robinson for level 6 ceiling rough in. Phone #: ###-#### Inspection requested via web by Tom Betty r/i ok partial ceiling level 6 corridor 06-A21 and breezeway
|
Electrical Rough-In | 1/26/2015 | 1/27/2015 | 1/27/2015 | A | PASS |
Rex Boyles
|
|
|
Contact Brandon Robinson for level 5 rough in. Phone #: ###-#### Inspection requested via web by Tom Betty level5 vestibule and alcove ceilings r/i ok. Level 6 east bathrooms ceilings r/i ok
|
Electrical Rough-In | 1/21/2015 | 1/22/2015 | 1/22/2015 | A | PASS |
Rex Boyles
|
|
|
Call Brandon for level 5 rough in Phone #: ###-#### Inspection requested via web by Tom Betty r/i ceiling ok movement corridor. Also discuss lighting control panel ok not to bring nuetrals into control panel with Toby. Also discuss conduits in front of transformer "not in the way of working space" and is ok with Dennis.
|
Electrical Rough-In | 12/16/2014 | 12/17/2014 | 12/17/2014 | P | PASS |
Rex Boyles
|
|
|
Contact Brandon Robinson for level 5 rough in inspection. Phone #: ###-#### Inspection requested via web by Tom Betty movement studio bathrooms and electrical room ceilings r/i ok
|
Electrical Rough-In | 12/10/2014 | 12/11/2014 | 12/11/2014 | A | PASS |
Rex Boyles
|
|
|
Call Brandon Robinson for level 5 ceiling rough in. Phone #: ###-#### Inspection requested via web by Tom Betty r/i ok level 5 soffits and level 4 electrical room ok to energize sw. gear
|
Electrical Rough-In | 12/5/2014 | 12/8/2014 | 12/8/2014 | P | PASS |
Rex Boyles
|
|
|
Cieling inspection level 1 contact Dennis Kienitz Phone #: ###-#### Inspection requested via web by Tom Betty kitchen and hall ceiling r/i ok
|
Electrical Rough-In | 11/21/2014 | 11/21/2014 | 11/21/2014 | P | PASS |
Rex Boyles
|
|
|
Tony Phone #: ###-#### r/i level 6 kitchen corridor walls and storage rooms ok
|
Final | 11/6/2014 | 11/7/2014 | 11/7/2014 | P | PASS |
Rex Boyles
|
|
|
Contact Brandon Robinson for level 6 kitchen rough in cover inspection. Phone #: ###-#### Inspection requested via web by Tom Betty r/i walls partial level 6
|
Electrical Rough-In | 11/3/2014 | 11/4/2014 | 11/4/2014 | P | PASS |
Rex Boyles
|
|
|
Level 4 ceiling rough in. Contact Brandon Robinson. Phone #: ###-#### Inspection requested via web by Tom Betty level 4 remainder of ceiling r/i except elevator lobby ok to cover
|
Electrical Rough-In | 10/31/2014 | 10/31/2014 | 10/31/2014 | A | PASS |
Rex Boyles
|
|
|
Level 1 kitchen ceiling rough in. Call Dennis Kienitz for walk through. Phone #: ###-#### Inspection requested via web by Tom Betty level 1 kitchen studio ceiling
|
Electrical Rough-In | 10/29/2014 | 10/30/2014 | 10/30/2014 | A | PASS |
Rex Boyles
|
|
|
Jon Mittlieder needs restroom walls on level 6 inspected. Phone #: ###-#### Inspection requested via web by Tom Betty r/i bath walls level 6 ok. r/i ceiling level 4 elevator area ok
|
Electrical Rough-In | 10/20/2014 | 10/21/2014 | 10/21/2014 | P | PART |
Rex Boyles
|
|
|
4th level soffit area rough in. Phone #: ###-#### Inspection requested via web by Tom Betty level 4 soffits and ceiling r/i ok see inspector set for exact areas
|
Electrical Rough-In | 10/20/2014 | 10/21/2014 | 10/21/2014 | A | PART |
Rex Boyles
|
|
|
Level 5 rough in for Brandon. Phone #: ###-#### Inspection requested via web by Tom Betty level 5 helix- r/i soffits and walls ok level 6 helix- columns and u. ground between columns only r/i ok see inspector set
|
Permanent Service | 10/17/2014 | 10/17/2014 | 10/17/2014 | P | PASS |
Rex Boyles
|
|
|
Please come to Lea Electric job trailer for breaker testing documentation. Phone #: ###-#### Inspection requested via web by Tom Betty p/s u/g n ok received performance test docs from switchgear manufacturer for gear as per 230.95 (C)
|
Permanent Service | 10/15/2014 | 10/15/2014 | 10/15/2014 | A | FAIL |
Rex Boyles
|
|
|
Call Jon. This inspection is in conjunction with inspection for permit ELE12-02982. Phone #: ###-#### Inspection requested via web by Tom Betty performance testing documents needed prior to energizing as per 230.95C
|
Electrical Rough-In | 10/7/2014 | 10/8/2014 | 10/8/2014 | A | PASS |
Rex Boyles
|
|
|
Level 5 soffit rough in. Phone #: ###-#### Inspection requested via web by Tom Betty level 1 stairwell lobby ceiling, level 3 stairwell service core soffit and level 5 soffit and multi purpose walls ok to cover
|
Electrical Rough-In | 9/29/2014 | 9/29/2014 | 9/29/2014 | P | PASS |
Rex Boyles
|
|
|
Level 3 Phone #: ###-#### Inspection requested via web by Tom Betty partial ceiling 3rd level
|
Electrical Rough-In | 9/22/2014 | 9/22/2014 | 9/22/2014 | P | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by Tom Betty r/i ok ceiling below movement studio
|
Electrical Rough-In | 9/18/2014 | 9/19/2014 | 9/19/2014 | P | PASS |
Rex Boyles
|
|
|
Call Brandon for level 4 in soffit rough in. Phone #: ###-#### Inspection requested via web by Tom Betty r/i ceiling under inspiration studio ok to cover
|
Electrical Rough-In | 9/17/2014 | 9/17/2014 | 9/17/2014 | P | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by Tom Betty go over fat grid ceiling submittals to confirm installation is acceptable. Additional supports have been installed onthese ceilings. r/i ok part of 3rd level ceiling helix
|
Electrical Rough-In | 9/15/2014 | 9/15/2014 | 9/15/2014 | P | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by Tom Betty level 5 motion studio and bathroom walls and all helix columns and walls r/i ok
|
Electrical Rough-In | 9/5/2014 | 9/8/2014 | 9/8/2014 | A | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by Tom Betty level 2 ceiling partial r/i ok
|
Electrical Rough-In | 9/5/2014 | 9/5/2014 | 9/5/2014 | P | PASS |
Rex Boyles
|
|
|
Level 2 soffit Phone #: ###-#### Inspection requested via web by Tom Betty r/i ok soffit level 2
|
Electrical Rough-In | 8/20/2014 | 8/21/2014 | 8/21/2014 | P | PASS |
Rex Boyles
|
|
|
Level four restroom area. Talk to Brandon. Phone #: ###-#### Inspection requested via web by Tom Betty r/i ok 1st floor bath ceilings, 3rd floor walls in electrical rooms, 4th floor bathroom walls
|
Electrical Rough-In | 8/7/2014 | 8/7/2014 | 8/7/2014 | P | PASS |
Rex Boyles
|
|
|
Level 1 Lobby Phone #: ###-#### Inspection requested via web by Tom Betty r/i ceiling ok waiting area A 015
|
Electrical Rough-In | 7/21/2014 | 7/22/2014 | 7/22/2014 | P | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by Tom Betty r/i ok slab level garden studio , middle section
|
Electrical Rough-In | 6/25/2014 | 6/25/2014 | 6/25/2014 | A | PASS |
Rex Boyles
|
|
|
2nd level rough in Phone #: ###-#### >> Inspection requested via web by Tom Betty rough in ok level 2 area A kitchen lobby walls
|
Electrical Rough-In | 6/23/2014 | 6/24/2014 | 6/24/2014 | P | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### >> Inspection requested via web by Tom Betty rough in ok remainder of exterior walls in multimedia 4 th floor not including pony wall
|
Electrical Rough-In | 6/19/2014 | 6/20/2014 | 6/20/2014 | P | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### >> Inspection requested via web by Tom Betty rough in ok -Level 1-lobby walls, level 3-maint. room walls, level4-multi media studio walls, inspiration studio walls, (level 5 makers studio walls see Arch. sheet A3-05-B)
|
Electrical Rough-In | 6/10/2014 | 6/11/2014 | 6/11/2014 | A | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### >> Inspection requested via web by Tom Betty rough in ok kitchen studio and trash compactor/mechanical riser room
|
Final | 6/5/2014 | 6/6/2014 | 6/6/2014 | P | CANC |
Rock A. Hudson
|
|
|
Same site as inspection for ELE-011385 same time period. Phone #: ###-#### >> Inspection requested via web by Tom Betty Foreman to check on this request and recall if needed
|
Electrical Rough-In | 5/30/2014 | 6/2/2014 | 6/2/2014 | P | PASS |
Rex Boyles
|
|
|
Any questions please call Jon Novak. Phone #: ###-#### >> Inspection requested via web by Vicki Moore rough in walls ok in bathrooms O1A-21 thru 24, and rooms 1A -31 thru 35
|
Final | 1/21/2014 | 1/22/2014 | 1/22/2014 | P | CANC |
Rock A. Hudson
|
|
|
Please contact Rob Crook for access Phone #: ###-#### >> Inspection requested via web by Tina Payne Needed inspection at 5310 w. state. Wrong permit requested
|
Conference | 1/21/2014 | 1/21/2014 | 1/21/2014 | P | DONE |
Rock A. Hudson
|
|
|
Contract Tony Keen at ###-####. Phone #: ###-#### >> Inspection requested via web by Tina Payne Discussed conduits and boxes installed in precast parking barriers. Contractor to verify 3rd party listing on company making barriers. APA Certified company listed on spec sheet for barriers
|
Final | 1/15/2014 | 1/15/2014 | 1/15/2014 | P | PASS |
Rock A. Hudson
|
|
|
lea electric Phone #: ###-#### 5th floor "jump" floor pour rough in ok cover
|
Electrical Rough-In | 12/19/2013 | 12/20/2013 | 12/20/2013 | A | PASS |
Rock A. Hudson
|
|
|
John Phone #: ###-#### Heat tape located in super columns rough in ok cover
|
Electrical Rough-In | 11/22/2013 | 11/25/2013 | 11/25/2013 | P | PASS |
Rock A. Hudson
|
|
|
Level 5 deck next to Myrtle. Phone #: ###-#### >> Inspection requested via web by Tony Keen 5 th floor second pour as noted on print rough in ok cover
|
Electrical Rough-In | 11/20/2013 | 11/21/2013 | 11/21/2013 | A | PASS |
Rock A. Hudson
|
|
|
Level 1 North side of Helix Phone #: ###-#### >> Inspection requested via web by Tony Keen Buil up level 1 floor pour as noted on print rough in ok cover
|
Electrical Rough-In | 10/30/2013 | 10/31/2013 | 10/31/2013 | A | PASS |
Rock A. Hudson
|
|
|
Level 4 south of helix Phone #: ###-#### >> Inspection requested via web by Tony Keen 4th floor ramp pour rough in ok cover
|
Electrical Rough-In | 10/23/2013 | 10/24/2013 | 10/24/2013 | P | PASS |
Rock A. Hudson
|
|
|
Level 5 PT deck. Top of the stair tower. Phone #: ###-#### >> Inspection requested via web by Tony Keen As noted on print 5th floor pour rough in ok cover
|
Electrical Rough-In | 10/14/2013 | 10/15/2013 | 10/15/2013 | A | PART |
Doug A Poedy
|
|
|
Rough in of ramp Phone #: ###-#### >> Inspection requested via web by Tony Keen. Ramp between 2nd and 3rd floor ok to cover.
|
Electrical Rough-In | 10/3/2013 | 10/4/2013 | 10/4/2013 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Tony Keen Ramp pour as noted on print rough in ok cover
|
Electrical Rough-In | 9/24/2013 | 9/25/2013 | 9/25/2013 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Tony Keen Ramp pour as noted on print rough in ok cover
|
Electrical Rough-In | 9/20/2013 | 9/23/2013 | 9/23/2013 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Tony Keen 4th floor helix pour as noted on print. Rough in ok cover
|
Electrical Rough-In | 9/17/2013 | 9/18/2013 | 9/18/2013 | P | PASS |
Rock A. Hudson
|
|
|
Level 4 parking garage rough in Phone #: ###-#### >> Inspection requested via web by Tony Keen 4th floor pour as noted on print rough in ok cover
|
Electrical Rough-In | 9/11/2013 | 9/11/2013 | 9/11/2013 | P | PASS |
Rock A. Hudson
|
|
|
John Phone #: ###-#### Parking garage basement air handling extrusion pour as noted on print rough in ok cover
|
Electrical Rough-In | 9/6/2013 | 9/9/2013 | 9/9/2013 | A | PASS |
Rock A. Hudson
|
|
|
john Phone #: ###-#### Ramp pour in as noted on print. Rough in ok cover
|
Electrical Rough-In | 8/27/2013 | 8/28/2013 | 8/28/2013 | P | PASS |
Rock A. Hudson
|
|
|
john Phone #: ###-#### 4th floor parking garage pour as noted on print. Rough in ok cover
|
Electrical Rough-In | 8/22/2013 | 8/22/2013 | 8/22/2013 | P | PASS |
Rock A. Hudson
|
|
|
john Phone #: ###-#### Helix 3rd floor pour rough in ok cover
|
Electrical Rough-In | 8/9/2013 | 8/12/2013 | 8/12/2013 | A | PASS |
Rock A. Hudson
|
|
|
john Phone #: ###-#### Ramp as noted on print pour rough in ok cover
|
Electrical Rough-In | 7/25/2013 | 7/26/2013 | 7/26/2013 | A | PASS |
Rock A. Hudson
|
|
|
john Phone #: ###-#### Helix 2nd floor pour as noted on print. Rough in ok cover
|
Electrical Rough-In | 7/18/2013 | 7/19/2013 | 7/18/2013 | A | PASS |
Rock A. Hudson
|
|
|
tony Phone #: ###-#### Outer ramp floor 1 to 2 rough in ok cover
|
Electrical Rough-In | 7/16/2013 | 7/17/2013 | 7/17/2013 | P | PASS |
Rock A. Hudson
|
|
|
John Phone #: ###-#### 3rd floor pour as noted on print rough in ok cover
|