Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberELE13-01487
StatusFinaled
Name ALLOWAY ELECTRIC CO INC
Site Address 1908 N 17TH ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - Addition: Installing electrical for garage i.e. receptacles, lighting, water heater.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/10/20137/10/20137/10/2013PPASS
DetailsRock A. Hudson
Please call Asher Sears if any questions Phone #: ###-#### >> Inspection requested via web by brad williams Final ok
Final7/8/20137/8/20137/8/2013PNR
DetailsRock A. Hudson
Please call Asher Sears if any questions Phone #: ###-#### >> Inspection requested via web by brad williams Devices changed, split unit has not been corrected yet.
Final7/2/20137/3/20137/3/2013AFAIL
DetailsRock A. Hudson
Please call Asher Sears if any questions Phone #: ###-#### >> Inspection requested via web by brad williams
400.8 Split system, flexible cord shall not pass through wall.
406.11 In all areas listed in 210.52 all 15 and 20 amp120 volt recepticals shall be tamper resistant.
Electrical Rough-In6/14/20136/14/20136/14/2013PPASS
DetailsRock A. Hudson
Asher Phone #: ###-#### Garage rough in ok cover
Electrical Rough-In6/12/20136/13/20136/13/2013AFAIL
DetailsRock A. Hudson
Please call Asher Sears, the electrician, if any questions Phone #: ###-#### >> Inspection requested via web by brad williams
300.4- NMB cable shall be secured at least 1 1/4" from framing member edge.
334.30 Flat cables shall not be sedured on edge.
HVAC classifies 18" above floor in garage as hazardous location, move recepticals up to 18" minimum to bottom.