Final | 7/3/2013 | 7/3/2013 | 7/3/2013 | P | PASS |
Daryl DeGrange
|
|
|
warren Phone #: ###-#### corrections done final ok
|
Final | 6/25/2013 | 6/25/2013 | 6/25/2013 | P | FAIL |
Daryl DeGrange
|
|
|
warren Phone #: ###-#### Grounding electrode conductor must terminate in ground bar not neutral bar. Complete panel directory, NEC 406.8(B) Requires receptacle installed in wet locations to be listed weather resistant type
|
Final | 6/19/2013 | 6/19/2013 | 6/19/2013 | P | FAIL |
Daryl DeGrange
|
|
|
warren Phone #: ###-#### Need ok seal in back of pump panel,support conduits below panel, install single ground rod.
|
Electrical Rough-In | 6/14/2013 | 6/17/2013 | 6/17/2013 | P | PASS |
Daryl DeGrange
|
|
|
Trench inspection please-Warren Phone #: ###-#### rough-in ok cover underground conduit to irrigation pump system in back yard
|