ELE-Aging Inspection | 8/11/2015 | 8/11/2015 | 8/11/2015 | | DONE |
Rock A. Hudson
|
|
|
Work completed under permit ele13-01595
|
Final | 8/11/2015 | 8/11/2015 | 8/11/2015 | P | PASS |
Rock A. Hudson
|
|
|
Work completed by contractor permit # ELE13-01595. Final ok
|
Permanent Service | 6/18/2013 | 6/19/2013 | 6/19/2013 | A | FAIL |
Daryl DeGrange
|
|
|
Richard Phone #: ###-#### NEC 230.24(B)(1) Vertical clearance for service-drop conductors. At the electrical service entrance to building,also at the lowest point of the drip loop of the building electrical entrance 10 ft. NEC 250.53(D)(2) Supplemental electrode required A metal underground water pipe shall be supplemented by an additional electrode
|