Permit Information
Permit NumberELE13-01605
StatusFinaled
Name CAPCHA JAVIER
Site Address 6410 W NORTHVIEW ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Permit to run electrical line from existing service to accessory structure and water feature in yard
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/27/20173/28/20173/28/2017APASS
DetailsTom Saunders
Javier Phone #: ###-####...

ok to final
ELE-Aging Inspection2/16/20172/16/20172/16/2017 DONE
DetailsTom Saunders
talked with homeowner...unaware needed to schedule final...will schedule
ELE-Aging Inspection7/13/20167/13/20167/13/2016 CANC
DetailsEric Story
too busy
ELE-Aging Inspection4/4/20164/4/20164/6/2016 PASS
DetailsRock A. Hudson
Still under construction
ELE-Aging Inspection1/4/20161/4/20161/4/2016 DONE
DetailsRock A. Hudson
Still under construction
ELE-Aging Inspection8/13/20158/13/20158/13/2015 CANC
DetailsRock A. Hudson
Too busy
Electrical Rough-In7/3/20147/3/20147/3/2014PPASS
DetailsBob Reichert
Javier Phone #: ###-#### ri ok, check breaker tie down at final, check for lb access at final right over panel
Electrical Rough-In7/1/20147/2/20147/2/2014AFAIL
DetailsDaryl DeGrange
Javier Phone #: ###-#### sub panel requires main breaker with tie down, still have nail plate and 1 1/4 issues
Electrical Rough-In6/30/20147/1/20147/1/2014AFAIL
DetailsRock A. Hudson
Javier Phone #: ###-#### 300.4- NM calbe shall be maintain 1 1/4" from framing surface.
300.4- Where NM cable is ran through bored holes less than 1 1/4" from framing surface they shall be protected from physical damage by nail plate.
Receptical outlets shall be located above 18" due to possible fuel storage.
Electrical Rough-In7/10/20137/11/20137/11/2013APASS
DetailsDaryl DeGrange
Javier Phone #: ###-#### rough-in ok cover trench to water feature
Electrical Rough-In7/2/20137/3/20137/3/2013APASS
DetailsDaryl DeGrange
Javier Phone #: ###-#### rough-in ok cover trench from house to shop
Conference6/21/20136/21/20136/21/2013PDONE
DetailsDaryl DeGrange
javier Phone #: ###-#### Discussed requirements for installing power underground to unattach structure.