Final | 8/6/2013 | 8/7/2013 | 8/7/2013 | A | PASS |
Rock A. Hudson
|
|
|
final on re inspection, any questions call Clint @ ###-#### Phone #: ###-#### >> Inspection requested via web by Andy Rose Final ok
|
Final | 8/6/2013 | 8/6/2013 | 8/6/2013 | A | FAIL |
Rock A. Hudson
|
|
|
final on remodel, any questions call Clint @ ###-#### Phone #: ###-#### >> Inspection requested via web by Andy Rose 1 receptical dead, disconnectivg means needed for water heater.
|
Electrical Rough-In | 8/2/2013 | 8/5/2013 | 8/5/2013 | P | PASS |
Rock A. Hudson
|
|
|
rough in of new wiring, will be ready at about 1:00 P:M. any questions call Clint @ ###-#### Phone #: ###-#### >> Inspection requested via web by Andy Rose Old NM cable removed. rough in ok cover
|
Electrical Rough-In | 7/19/2013 | 7/22/2013 | 7/22/2013 | A | PASS |
Rock A. Hudson
|
|
|
Rough in of new wiring for bathroom and kitchen any questions call Clint @ ###-#### Phone #: ###-#### >> Inspection requested via web by Andy Rose contractor to increase valuation, call back to confirm removal of NM cable around bath door and floor. Bath and kitchen rough in ok cover
|
Conference | 6/24/2013 | 6/24/2013 | 6/24/2013 | P | DONE |
Rock A. Hudson
|
|
|
need conference on electrical, please call Francis @ ###-#### or ###-####. would like to meet at site at 1:00 if possible. Phone #: ###-#### >> Inspection requested via web by Andy Rose Discussed existing wiring pulled through panel. New panel to unit and existing panel to be gutted and used as junction point.
|