Final | 10/7/2013 | 10/8/2013 | 10/8/2013 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Greg Traudt Final ok
|
Final | 10/2/2013 | 10/3/2013 | 10/3/2013 | P | PART |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Greg Traudt 680.51(A)- Outdoor fountain shall be GFCI protected. BBQ electrical unfinished. Shall complete panel schedules. Patrtial final ok
|
Rough-In Permanent Service | 7/4/2013 | 7/5/2013 | 7/5/2013 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Greg Traudt Rough in ok cover p/s u/g n ok
|
Rough-In Permanent Service | 7/3/2013 | 7/3/2013 | 7/3/2013 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Greg Traudt 300.4- Nail plates needed to protect wiring from physical damage in nook,quest bath, utility, and above AV panel. 300.4 NM cable secured less than 1 1/4" from surface of framing member in m. closet, above x-mas switch, several upstairs. 210.52 General purpose receptical required in study left as entered. 334.23 NM cable shall be protected from physical damage where run less than 6' from attic access. 314.4 Metal boxes shall be bonded and grounded per artical 250.
|