Final | 8/19/2013 | 8/19/2013 | 8/19/2013 | P | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey corrections done final ok
|
Final | 8/16/2013 | 8/16/2013 | 8/16/2013 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey 210.12(B)- All 120 volt recepticals shall have arc-fault protection. up vanity recepticals in bedrooms. AC unit overcurrent protection, 35 amp max 30 amp installed. Upstairs bath fan not working.
|
Rough-In Permanent Service | 7/7/2013 | 7/8/2013 | 7/8/2013 | A | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey rough-in p/s u/g n ok
|