Final | 8/25/2013 | 8/26/2013 | 8/26/2013 | A | PASS |
Rock A. Hudson
|
|
|
Xformer gone and data supported off ceiling. Please call in advance for access. Thanks Phone #: ###-#### >> Inspection requested via web by Rex Boyles No card posted final ok
|
Final | 8/20/2013 | 8/21/2013 | 8/21/2013 | A | FAIL |
Rock A. Hudson
|
|
|
Please call for access at least 30 min in advance. Thanks Phone #: ###-#### >> Inspection requested via web by Rex Boyles 300.11 Ceiling grid shall not provide support for cables or raceways. Transformer shall be removed that feeds next door unit and raceways must be repaired.
|