ELE-Aging Inspection | 3/17/2017 | 3/17/2017 | 3/20/2017 | | DONE |
James Ady
|
|
|
Finaled permit
|
Final | 3/20/2017 | 3/20/2017 | 3/20/2017 | P | PASS |
James Ady
|
|
|
Food truck No long there. Permit final ok
|
ELE-Aging Inspection | 7/15/2016 | 7/15/2016 | 7/15/2016 | | CANC |
Bob Reichert
|
|
|
too busy
|
ELE-Aging Inspection | 4/5/2016 | 4/5/2016 | 4/6/2016 | | CANC |
Bob Reichert
|
|
|
too busy
|
Final | 1/8/2015 | 1/8/2015 | 1/8/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Contact: Brian Gee Phone #: ###-#### Inspection requested via web by Deb Gooden 406.8(A)- A receptacle installed in a wet location shall have an enclosure that is weatherproof with the attachment plug inserted or removed. * No access to trailer to verify GFCI protection of 120 volt 15 or 20 amp receptical outlets and breaker blanks previously noted.
|
Permanent Service | 8/23/2013 | 8/23/2013 | 8/23/2013 | P | PASS |
Bob Reichert
|
|
|
Contact: Darby Talbot Phone #: ###-#### >> Inspection requested via web by Deb Gooden will final when trailer done, p/s o/h n ok
|
Permanent Service | 8/22/2013 | 8/22/2013 | 8/22/2013 | A | FAIL |
Bob Reichert
|
|
|
Contact: Jesse Phone #: ###-#### >> Inspection requested via web by Deb Gooden talked to contractor, shall provide fgci protection for cord connected trailer, shall fix trailer by strap riser, strap mc, provide breaker blanks, provide riser abrasion protection, strain relief for cord, cord shall be minimun #4 outdoor heavy duty, w rated, cord cap fixed, gfci protection
|
Final | 8/16/2013 | 8/16/2013 | 8/16/2013 | P | NR |
Bob Reichert
|
|
|
Contact: Darby Talbot. Phone #: ###-#### >> Inspection requested via web by Deb Gooden called, contractor shall call for p/s, IPCO requires minimum 6"x6" pole, shall provide for inspection of food vendor for safety compliance and or listing, shall not use # 10 for service for food truck if 50A breaker in panel, shall identify breakers in panel
|