Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberELE13-02313
StatusFinaled
Name BENDER ELECTRIC SERVICES
Site Address 1515 W STATE ST
Project NameRite Aid Tenant Improvement
Customer Number 
ePlanReviewNo
Description
Electrical Permit - Alteration: Remodel of exsiting Rite Aid store and pharmacy. New lighting and power, some refrigeration.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/20/201311/21/201311/22/2013PPASS
DetailsRock A. Hudson
Phone #: ###-#### >> Inspection requested via web by kendall bender No card posted lighting retro final ok
Electrical Rough-In10/17/201310/17/201310/17/2013APASS
DetailsRock A. Hudson
Pharmacy ceiling and pharmacy entry ceiling Phone #: ###-#### >> Inspection requested via web by kendall bender Contractor to leave tile out of 1 spot to check receptical is removed in phamacy above grid by drive thru window. Ceiling rough in ok cover
Electrical Rough-In10/16/201310/16/201310/16/2013PPASS
DetailsRock A. Hudson
Remainder of sales floor cieling Phone #: ###-#### >> Inspection requested via web by kendall bender Sales floor central area ceiling rough in ok cover
Electrical Rough-In10/14/201310/14/201310/14/2013APART
DetailsDaryl DeGrange
Partial sales floor area Phone #: ###-#### >> Inspection requested via web by kendall bender Partial rough-in ok cover east eleven rows and west five rows of recessed luminaires. Reattach strip fixtures above rear center sales floor ceiling grid before next ceiling cover inspection
Electrical Rough-In10/11/201310/11/201310/11/2013PPART
DetailsRock A. Hudson
Partial ceiling at west end of store over refrigeration Phone #: ###-#### >> Inspection requested via web by kendall bender Ceiling rough in west end to change in elevation. Rough in ok cover.
Electrical Rough-In10/8/201310/9/201310/9/2013AFAIL
DetailsRock A. Hudson
partial ceiling Phone #: ###-#### >> Inspection requested via web by kendall bender BCC 4-10-32- Code violation not to be retained,
NEC 300.11- Cables and raceways shall not be supported by ceiling grid.
800.25- Abandoned cables shall be removed or tagged for future use.
800.133- Raceways shall not be used as support for communication cables
Electrical Rough-In9/12/20139/13/20139/13/2013APASS
DetailsRock A. Hudson
New walls at pharmacy at Northeast corner inside store. Rouhin walls only. Phone #: ###-#### >> Inspection requested via web by kendall bender Pharmacy wall rough in ok cover