Final | 11/20/2013 | 11/21/2013 | 11/22/2013 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by kendall bender No card posted lighting retro final ok
|
Electrical Rough-In | 10/17/2013 | 10/17/2013 | 10/17/2013 | A | PASS |
Rock A. Hudson
|
|
|
Pharmacy ceiling and pharmacy entry ceiling Phone #: ###-#### >> Inspection requested via web by kendall bender Contractor to leave tile out of 1 spot to check receptical is removed in phamacy above grid by drive thru window. Ceiling rough in ok cover
|
Electrical Rough-In | 10/16/2013 | 10/16/2013 | 10/16/2013 | P | PASS |
Rock A. Hudson
|
|
|
Remainder of sales floor cieling Phone #: ###-#### >> Inspection requested via web by kendall bender Sales floor central area ceiling rough in ok cover
|
Electrical Rough-In | 10/14/2013 | 10/14/2013 | 10/14/2013 | A | PART |
Daryl DeGrange
|
|
|
Partial sales floor area Phone #: ###-#### >> Inspection requested via web by kendall bender Partial rough-in ok cover east eleven rows and west five rows of recessed luminaires. Reattach strip fixtures above rear center sales floor ceiling grid before next ceiling cover inspection
|
Electrical Rough-In | 10/11/2013 | 10/11/2013 | 10/11/2013 | P | PART |
Rock A. Hudson
|
|
|
Partial ceiling at west end of store over refrigeration Phone #: ###-#### >> Inspection requested via web by kendall bender Ceiling rough in west end to change in elevation. Rough in ok cover.
|
Electrical Rough-In | 10/8/2013 | 10/9/2013 | 10/9/2013 | A | FAIL |
Rock A. Hudson
|
|
|
partial ceiling Phone #: ###-#### >> Inspection requested via web by kendall bender BCC 4-10-32- Code violation not to be retained, NEC 300.11- Cables and raceways shall not be supported by ceiling grid. 800.25- Abandoned cables shall be removed or tagged for future use. 800.133- Raceways shall not be used as support for communication cables
|
Electrical Rough-In | 9/12/2013 | 9/13/2013 | 9/13/2013 | A | PASS |
Rock A. Hudson
|
|
|
New walls at pharmacy at Northeast corner inside store. Rouhin walls only. Phone #: ###-#### >> Inspection requested via web by kendall bender Pharmacy wall rough in ok cover
|