Final | 12/5/2013 | 12/6/2013 | 12/6/2013 | A | PASS |
Daryl DeGrange
|
|
|
Key in front outlet cover Phone #: ###-#### >> Inspection requested via web by TOM BICANDI correction done, final ok
|
Final | 11/27/2013 | 11/27/2013 | 11/27/2013 | P | FAIL |
Bob Reichert
|
|
|
Addresses are garage codes Phone #: ###-#### >> Inspection requested via web by TOM BICANDI called, bathroom gfci protection shall operate
|
Permanent Service | 9/20/2013 | 9/23/2013 | 9/23/2013 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by TOM BICANDI corrections made, p/s u/g n ok, 3 meters req,d
|
Permanent Service | 9/19/2013 | 9/19/2013 | 9/19/2013 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by TOM BICANDI called, shall identify meters
|
Electrical Rough-In | 9/4/2013 | 9/4/2013 | 9/4/2013 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by TOM BICANDI corrections made, ri ok
|
Electrical Rough-In | 9/3/2013 | 9/4/2013 | 9/4/2013 | A | FAIL |
Bob Reichert
|
|
|
3 unit condo Phone #: ###-#### >> Inspection requested via web by TOM BICANDI called, shall install receptacles per NEC 210, 314 shall flush outside boxes, 334 shall protect attic access cables, 300 shall provide 1 1/4" protection in bored holes, 110 shall close open ko in panel, BCC shall terminate cable in box (#10 in west garage), west panel shall be mounted in wall correctly
|