Final | 1/13/2014 | 1/14/2014 | 1/14/2014 | P | PASS |
Daryl DeGrange
|
|
|
John Phone #: ###-#### corrections done, final ok
|
Final | 12/16/2013 | 12/17/2013 | 12/17/2013 | P | FAIL |
Daryl DeGrange
|
|
|
John Phone #: ###-#### NEC 210.8 (2) All kitchen 15 and 20 ampere receptacles shall have GFCI protection NEC 210.52(B)(3) Kitchen countertop shall be supplied by no fewer than two small appliance branch circuits. NEC 406.11 All 15 and 20 ampere 120 volt receptacle in dwelling units shall be listed tamper resistant receptacles
|
Conference | 10/7/2013 | 10/7/2013 | 10/7/2013 | P | DONE |
Daryl DeGrange
|
|
|
Discussed with homeowner requirements for final inspection
|
Electrical Rough-In | 10/4/2013 | 10/7/2013 | 10/7/2013 | P | DONE |
Daryl DeGrange
|
|
|
john please call before going out Phone #: ###-#### Rough-in ok cover upstairs addition
|
Electrical Rough-In | 10/3/2013 | 10/4/2013 | 10/4/2013 | P | FAIL |
Daryl DeGrange
|
|
|
John Egbert-please call at least 30 mins prior to insepction Phone #: ###-#### Grounding requires mechanical connections(wire nuts)
|
Electrical Rough-In | 9/20/2013 | 9/23/2013 | 9/23/2013 | P | NR |
Daryl DeGrange
|
|
|
After 3:00 pm please-John Phone #: ###-#### Not ready
|
Conference | 9/9/2013 | 9/9/2013 | 9/9/2013 | P | DONE |
Daryl DeGrange
|
|
|
Discussed with homeowner electrical requirements for wiring upstairs living area
|
Conference | 9/5/2013 | 9/6/2013 | 9/6/2013 | P | CANC |
Bob Reichert
|
|
|
Call ahead for access - john Phone #: ###-#### owner wanted to confer Monday, not Friday
|