Final | 9/24/2013 | 9/25/2013 | 9/25/2013 | A | PASS |
Bob Reichert
|
|
|
re-inspect after corrections made. Phone #: ###-#### >> Inspection requested via web by Robert Carter ok final
|
Final | 9/22/2013 | 9/23/2013 | 9/23/2013 | A | FAIL |
Daryl DeGrange
|
|
|
panel changed Phone #: ###-#### >> Inspection requested via web by Robert Carter NEC 110.26(A) Working space for service equipment, NEC 408.4 complete panel directory circiuts #13 & 19 Bond hot and cold water pipes at water heater
|
Permanent Service | 9/10/2013 | 9/11/2013 | 9/11/2013 | A | PASS |
Daryl DeGrange
|
|
|
inspection to get the power turned on after it has been off for more than a year Phone #: ###-#### >> Inspection requested via web by Robert Carter p/s o/h rec ok
|