Final | 12/23/2013 | 12/23/2013 | 12/23/2013 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by George Pascua corrections made, ok final, signed card
|
Final | 12/20/2013 | 12/23/2013 | 12/23/2013 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by George Pascua called, corrections not made, shall provide gfci for refrigerator
|
Final | 11/26/2013 | 11/27/2013 | 11/27/2013 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by George Pascua called, NEC 408.4 circuit directory shall be clear concise and evident for purpose such as room number for receptacles, 210.8(B)(5) receptacle within 6' of sink shall be gfci protected, 406.4(D) receptacle face shall be flush with or project from faceplate, BCC shall install bathroom receptacle, hall lights, and receptacles shall operate near break room, BCC shall post address or suite number
|
Electrical Rough-In | 11/21/2013 | 11/21/2013 | 11/21/2013 | P | PASS |
Bob Reichert
|
|
|
ceiling insp// George Phone #: ###-#### corrections made, ok cover ceiling
|
Electrical Rough-In | 11/19/2013 | 11/20/2013 | 11/20/2013 | A | FAIL |
Bob Reichert
|
|
|
Ceiling lighting layout - George Phone #: ###-#### called, NEC 324.23 shall support boxes, 358.30 shall support emt, 300.11 raceway shall not support other wiring, 725.25 shall remove abandoned wiring, 300.11 shall not use grid or tiles for support of whips
|
Electrical Rough-In | 10/8/2013 | 10/9/2013 | 10/9/2013 | A | PASS |
Bob Reichert
|
|
|
George Phone #: ###-#### corrections made, ok cover walls only
|
Electrical Rough-In | 10/4/2013 | 10/4/2013 | 10/4/2013 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by George Pascua called, left correction notice, to owner and permit, NEC 330.30(B) shall secure mc cable within 12" of box, 352.30(A) shall secure pvc within 3' of box
|