Permit Information
Permit NumberELE13-02810
StatusFinaled
Name RUNDLE ELECTRIC
Site Address 3110 W STATE ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - New: Complete electrical for new Jackson''s building to replace the old building that is being demolished. Includes site lighting.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/29/20141/29/20141/29/2014APASS
DetailsRock A. Hudson
Final inspect at Jacksons. Contact is Justin Bieker. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery Final ok
Final1/23/20141/23/20141/23/2014PNR
DetailsBob Reichert
This is a Partial-final. Contact is Justin Bieker. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery still putting down tile, no access, still installing equipment, contractor to verify listing for walk-in coolers
Electrical Rough-In12/31/201312/31/201312/31/2013PPASS
DetailsRock A. Hudson
Ceiling grid inspection for all areas with grid ceiling. Contact on job is Justin Bieker. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery Ceiling rough in ok cover
Permanent Service12/4/201312/4/201312/4/2013APASS
DetailsRock A. Hudson
Service inspect. Contact is Justin Bieker. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery p/s u/g n ok
Electrical Rough-In11/27/201312/2/201312/2/2013ACANC
DetailsRock A. Hudson
Rough inspection of new interior wall in the warehouse area. Contact is Jay Sprik. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery Inspection cancelled from web by: Richard Montgomery
Electrical Rough-In11/27/201311/27/201311/27/2013PPART
DetailsRock A. Hudson
Inspect for CT Can service, soffit in sales area and parking lot pole bases. Contact is Justin Bieker. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery Pole bases and sales soffit rough in ok cover. Service 250.24(A)(1)- Grounding electrode conductor connection shall be made at an accessible point and shall terminate at the same bus bar or terminal as the grounded conductor.
Electrical Rough-In11/26/201311/27/201311/27/2013ACANC
DetailsRock A. Hudson
Inspect for CT Can, soffit in sales area and parking lot pole bases. Contact is Justin Bieker. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery Inspection cancelled from web by: Richard Montgomery
Electrical Rough-In11/21/201311/22/201311/22/2013APASS
DetailsRock A. Hudson
Ground inspection SE edge of property. Contact is Justin Bieker. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery Perimeter underground to 3 pole lights and front compressor. rough in ok cover
Electrical Rough-In11/20/201311/20/201311/20/2013PPASS
DetailsRock A. Hudson
Ceiling inspect for the restrooms. Contact is Justin Bieker. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery Rough in ok cover
Electrical Rough-In11/19/201311/19/201311/19/2013APART
DetailsBob Reichert
Ground inspection. Contact is Justin Bieker. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery u/g except perimeter and island area ok cover, told ok cover entry with drive access only- about 10'
Electrical Rough-In11/18/201311/18/201311/18/2013PPASS
DetailsDaryl DeGrange
Interior walls rough-in. Contact on job is Justin Bieker. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery rough-in ok cover walls
Electrical Rough-In11/13/201311/14/201311/14/2013APASS
DetailsRock A. Hudson
Rough inspect exterior walls near coolers. Contact is Justin Bieker. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery South cooler wall rough in ok cover
Electrical Rough-In10/18/201310/21/201310/21/2013APASS
DetailsRock A. Hudson
Ground work inspection panel area only. Contact is Jay Sprik. Phone #: ###-#### >> Inspection requested via web by Richard MontgomeryUnderground from buiding service and control to pumps and misc. Rough in ok cover
Electrical Rough-In10/18/201310/18/201310/18/2013PPART
DetailsRock A. Hudson
Interior underground inspection. Contact on the job is Jay Sprik. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery 514.9- All conduits that run to or through hazardous locations shall have seals at both ends. Non metalloc conduits ok 2' and deeper. Where conduit is less than 2' it shall be rigid or IMC. Rough in central area ok cover.
Electrical Rough-In10/8/201310/9/201310/9/2013APASS
DetailsRock A. Hudson
This is an inspect for the uffer ground. Contact is Jay Sprik. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery Rough in ok cover