Final | 11/19/2013 | 11/19/2013 | 11/19/2013 | A | PASS |
Daryl DeGrange
|
|
|
the key on the left side of the front door up on a rock ledge, thx. Phone #: ###-#### >> Inspection requested via web by Stephen Kren final ok
|
Electrical Rough-In | 10/29/2013 | 10/30/2013 | 10/30/2013 | A | PASS |
Daryl DeGrange
|
|
|
The corrections have been fixed, the key is on the left side of the front door under the ledge, any questions please let m know, thanks. Phone #: ###-#### >> Inspection requested via web by Stephen Kren rough-in ok cover walls
|
Electrical Rough-In | 10/28/2013 | 10/29/2013 | 10/29/2013 | A | FAIL |
Daryl DeGrange
|
|
|
The key is on the left side of the entrance under one of the rock ledges, please call for any questions, thx, TW. Phone #: ###-#### >> Inspection requested via web by Stephen Kren NEC 330.12(1) nail plates, Missing mudrings
|
Electrical Rough-In | 10/14/2013 | 10/14/2013 | 10/14/2013 | P | CANC |
Daryl DeGrange
|
|
|
Any questions please call, thanks, TW. Phone #: ###-#### >> Inspection requested via web by Stephen Kren Inspection cancelled from web by: Stephen Kren
|