Final | 5/8/2014 | 5/8/2014 | 5/8/2014 | P | PASS |
Bob Reichert
|
|
|
Garage code 1969E Phone #: ###-#### >> Inspection requested via web by Alan Lusk ok final
|
Electrical Rough-In | 12/17/2013 | 12/18/2013 | 12/18/2013 | P | PASS |
Bob Reichert
|
|
|
Need roughin inspection for shop building. Phone #: ###-#### >> Inspection requested via web by Alan Lusk ri ok
|
Rough-In Permanent Service | 12/6/2013 | 12/8/2013 | 12/9/2013 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Alan Lusk corrections made, ri ok, p/s u/g n ok
|
Rough-In Permanent Service | 12/6/2013 | 12/6/2013 | 12/6/2013 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Alan Lusk 200.6- All grounded conductors at service shall be identified. 300.4- NM cables ran through bored holes less than 1 1/4" from framing surface shall be protected from physical damage. 334.15(B)- NM cable in kitchen ablove 3 gang not contained with in stud bay. 334.30- NM cable shall be secured with in 4 1/2' of passing through verital hole and with 12" of boxes. S/L to out soffit cans, spare bed, spare bath.
|
Electrical Rough-In | 11/27/2013 | 11/27/2013 | 11/27/2013 | P | PASS |
Bob Reichert
|
|
|
Need approval to cover trench. Phone #: ###-#### >> Inspection requested via web by Alan Lusk ok cover u/g house to garage
|
Electrical Rough-In | 10/14/2013 | 10/15/2013 | 10/15/2013 | A | PASS |
Bob Reichert
|
|
|
alen Phone #: ###-#### u/g for 4 floor boxes only ok cover
|