Final | 1/6/2014 | 1/6/2014 | 1/6/2014 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Lynn Cable ok final, signed card
|
Electrical Rough-In | 12/2/2013 | 12/3/2013 | 12/3/2013 | P | PASS |
Rock A. Hudson
|
|
|
Ready for ceiling inspection Phone #: ###-#### >> Inspection requested via web by Lynn Cable Exit and emergency not in yet, tile to be left to inspect support of boxes. Ceiling rough in ok cover
|
Electrical Rough-In | 11/30/2013 | 12/2/2013 | 12/2/2013 | A | FAIL |
Bob Reichert
|
|
|
Should be open for ceiling inspection. Phone #: ###-#### >> Inspection requested via web by Lynn Cable called, left correction notice, BCC no violations shall be retained, 725.25 shall remove abandoned cables, 300.11(B) raceways shall not be used as support for other raceways unless identified for purpose, 300.11(A) shall not support cable by grid or tile, 330.30(B) mc shall be secured within 12" of box, 314.23(E) raceways shall not support box, 314. 25 boxes shall be closed, 314.7(B) shall provide abrasion protection for conductors in metal boxes
|
Electrical Rough-In | 11/27/2013 | 11/29/2013 | 11/29/2013 | A | NH |
Bob Reichert
|
|
|
Above ceiling inspection. Lock box is in stair well and combo is 9766 or 6679 Phone #: ###-#### >> Inspection requested via web by Lynn Cable called doors locked to building, said to recall for Monday
|
Electrical Rough-In | 10/24/2013 | 10/24/2013 | 10/24/2013 | P | PASS |
Bob Reichert
|
|
|
Cover inspection for walls only. Phone #: ###-#### >> Inspection requested via web by Lynn Cable walls only ok cover
|
Electrical Rough-In | 10/11/2013 | 10/11/2013 | 10/11/2013 | P | PASS |
Bob Reichert
|
|
|
u/g only
|