Permanent Service | 4/2/2014 | 4/2/2014 | 4/2/2014 | P | PASS |
Bob Reichert
|
|
|
Contact: Brian Gee - Please call before going Phone #: ###-#### >> Inspection requested via web by Deb Gooden corrections made, p/s o/h rec ok
|
Final | 4/2/2014 | 4/2/2014 | 4/2/2014 | P | PASS |
Bob Reichert
|
|
|
Contact: Brian Gee - Please call before going Phone #: ###-#### >> Inspection requested via web by Deb Gooden ok final
|
Final | 3/31/2014 | 3/31/2014 | 3/31/2014 | P | FAIL |
Bob Reichert
|
|
|
Contact: Brian Gee Phone #: ###-#### >> Inspection requested via web by Deb Gooden called, shall repair bond screw in service panel per NEC 250
|
Permanent Service | 3/11/2014 | 3/12/2014 | 3/12/2014 | P | FAIL |
Bob Reichert
|
|
|
Contact: Marty Vanness Phone #: ###-#### >> Inspection requested via web by Deb Gooden met contractor,,NEC 110.26 shall provide work space at panel
|
Final | 3/10/2014 | 3/11/2014 | 3/11/2014 | P | NR |
Bob Reichert
|
|
|
Contact: Marty Vanness Phone #: ###-#### >> Inspection requested via web by Deb Gooden contractor still working on, will re-call
|
Permanent Service | 3/10/2014 | 3/11/2014 | 3/11/2014 | P | NR |
Bob Reichert
|
|
|
Contact: Marty Vanness Phone #: ###-#### >> Inspection requested via web by Deb Gooden met contractor, he will recall
|
Conference | 10/16/2013 | 10/16/2013 | 10/16/2013 | A | DONE |
Bob Reichert
|
|
|
Contact: Brian Gee, please call 1/2 hour before going Phone #: ###-#### >> Inspection requested via web by Deb Gooden talked about bringing service up to code to re-energize, service conductors too low, no grounding, mast too small, illegal a/c tap through meter
|