Final | 11/6/2013 | 11/7/2013 | 11/7/2013 | P | PASS |
Doug A Poedy
|
|
|
The panel is labeled and ready for a final insp, the access CODE IS 4353, thx. Phone #: ###-#### >> Inspection requested via web by Stephen Kren
|
Permanent Service | 10/28/2013 | 10/29/2013 | 10/29/2013 | A | PASS |
Daryl DeGrange
|
|
|
ACCESS CODE - 4353. The water piping has been bonded, thanks, TW. Phone #: ###-#### >> Inspection requested via web by Stephen Kren correction done, p/s u/g rec ok
|
Permanent Service | 10/28/2013 | 10/28/2013 | 10/28/2013 | A | FAIL |
Daryl DeGrange
|
|
|
ACCESS CODE 4353, the corrections have been fixed, any questions please let me know, thanks, TW. Phone #: ###-#### >> Inspection requested via web by Stephen Kren NEC 250.52 Metal water pipe entering structure is required to be bonded within first five feet.
|
Permanent Service | 10/18/2013 | 10/18/2013 | 10/18/2013 | A | FAIL |
Bob Reichert
|
|
|
There hasn''t been a meter at this location for over a year, Idaho Power is requiring an inspection of the service before powering. The access code is 4353, thanks, TW. Phone #: ###-#### >> Inspection requested via web by Stephen Kren called, left message, shall bring grounding up to code, strap riser, id breakers, fix and recall for p/s
|