Temporary Service | 10/24/2013 | 10/24/2013 | 10/25/2013 | P | PASS |
Bob Reichert
|
|
|
Temp power pole Phone #: ###-#### >> Inspection requested via web by kendall bender corrections made, t/s o/h n ok
|
Temporary Service | 10/23/2013 | 10/24/2013 | 10/24/2013 | A | FAIL |
Bob Reichert
|
|
|
East end of lot behind and between pads Phone #: ###-#### >> Inspection requested via web by kendall bender called, left correction notice, NEC 400.5(A) ampacity #6 SOOW 45 A, breaker too large, BCC no address posted, no job id sticker, NEC 408.4 shall provide circuit directory,250.53(G) upper end of electrode shall be flush with or below ground, 406.8(B) 125 and 250V receptacles shall be listed weather resistant type
|