Temporary Service | 11/15/2013 | 11/15/2013 | 11/18/2013 | P | PASS |
Daryl DeGrange
|
|
|
HP. Temp service. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy t/s o/h n ok
|
Permanent Service | 10/30/2013 | 10/31/2013 | 10/31/2013 | P | FAIL |
Daryl DeGrange
|
|
|
HP. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy Idaho Power Company requires pressure treated 6X6 NEC 230.42(B)(2) Requires at least twelve feet of clearance at drip loop NEC 240.24 Highest available location a circuit breaker can be installed is 6 ft. 7 inches
|