Final | 1/13/2014 | 1/13/2014 | 1/13/2014 | P | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov correction done, final ok
|
Final | 1/9/2014 | 1/9/2014 | 1/9/2014 | P | FAIL |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov NEC 210.8 (7) Laundry, utility and wet bar sinks. Where the receptacle are installed within 6 ft. of the outside edge of the sink requires GCFI protection.
|
Rough-In Permanent Service | 11/6/2013 | 11/7/2013 | 11/7/2013 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov Rough in ok cover p/s u/g n ok
|
Rough-In Permanent Service | 11/6/2013 | 11/6/2013 | 11/6/2013 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov Corrections not complete. 300.4 NM cable shall be protected from physical damage where ran through bored holes and 1 1/4" is not maintained from stud surface. 300.2(C)(1)- All conductors shall have a insulating rating equal to the max voltage in an enclosure.
|
Rough-In Permanent Service | 11/4/2013 | 11/4/2013 | 11/4/2013 | P | FAIL |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov BCC Unlawful to conceal electrical wiring until inspection has been performed. Weatherization has also been performed before inspection NEC 324.23 Guard strips required for all cables crossing over trusses within 6 ft. of attic access. NEC 334.30 Shall staple NM cable within fixture box. Hall fixture top of stairs
|