Permit Information
Permit NumberELE13-03066
StatusFinaled
Name HIGH COUNTRY ELECTRIC
Site Address 1520 W STATE ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - Alteration: INSTALL ELECTRICICAL DEVICES PER PLANS AND SPEC
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/18/20144/18/20144/18/2014PPASS
DetailsRex Boyles
Phone #: ###-#### >> Inspection requested via web by Karl Paige final ok first floor
Electrical Rough-In3/13/20143/14/20143/14/2014PPASS
DetailsRex Boyles
Phone #: ###-#### >> Inspection requested via web by Karl Paige all receptacles are now hospital grade on 2nd floor except for exam rooms 9,10,11and 12, there was no work in these rooms.. all receptacles on first floor are now hospital grade in exam rooms. rough in ok
Electrical Rough-In3/13/20143/14/20143/13/2014ACANC
DetailsRex Boyles
hospital grade receptacles in exam rooms that we remodeled call so we can meet you on site Phone #: ###-#### >> Inspection requested via web by Karl Paige Inspection cancelled from web by: Karl Paige
Electrical Rough-In3/11/20143/11/20143/11/2014PFAIL
DetailsRock A. Hudson
517.18(B)- General care area receptical outlets shall be listed hospital grade type.
BCC 4-05-32- Code violations not to be retained, Other areas that have been improved in general care areas shall also have listed hospital grade receptical outlets installed.
Electrical Rough-In2/27/20142/27/20142/27/2014APASS
DetailsRex Boyles
temporary occupancy for phase 2 on first floor so tenant can move from phase 3 area into phase 2 area Phone #: ###-#### >> Inspection requested via web by Karl Paige install blank plate at existing toilet and either GFI or blank plate at box within 6 feet of sink in exam room before final inspection is called in.
Electrical Rough-In2/24/20142/24/20142/24/2014PPASS
DetailsRex Boyles
ceiling cover Phone #: ###-#### >> Inspection requested via web by Karl Paige ceiling ok for cover
Electrical Rough-In2/21/20142/21/20142/21/2014PPART
DetailsRock A. Hudson
ceiling cover 1st floor Phone #: ###-#### >> Inspection requested via web by Karl Paige all ok except open j box in waiting room and strapping of mc cable within 12" of box and seismic on fixtures in waiting room 132. ok for borders in ceiling.
Electrical Rough-In2/20/20142/20/20142/20/2014PFAIL
DetailsBob Reichert
ceiling cover first floor Phone #: ###-#### >> Inspection requested via web by Karl Paige called, told to see on-line items to correct, did ok part ceiling by reception desk only, shall close open box, add exrension rings, staple mc, emt, remove abandoned cable, provide ko seal, add seismic wires, BCC no violations shall be retained
Electrical Rough-In1/28/20141/28/20141/28/2014APASS
DetailsRock A. Hudson
1st floor wall cover Phone #: ###-#### >> Inspection requested via web by Karl Paige Wall rough in ok cover
Electrical Rough-In1/5/20141/6/20141/6/2014ACANC
DetailsRock A. Hudson
final for phase 1 of 2 phases Phone #: ###-#### >> Inspection requested via web by Karl Paige Needed temp final for phase 1
Final1/6/20141/6/20141/6/2014PPART
DetailsRock A. Hudson
final for phase 1 of 2 phases Phone #: ###-#### >> Inspection requested via web by Karl Paige Basement and 2nd floor ok occupy temp final ok
Electrical Rough-In12/31/201312/31/201312/31/2013PPASS
DetailsRock A. Hudson
ceiling cover inspection basement Phone #: ###-#### >> Inspection requested via web by Karl Paige Basement ceiling rough in ok cover
Electrical Rough-In12/29/201312/30/201312/30/2013AFAIL
DetailsDaryl DeGrange
ceiling cover 2nd floor and basement Phone #: ###-#### >> Inspection requested via web by Karl Paige Basement level NEC 800.25 The accessible portionof abandoned communnication cables shall be removed. Support MC cables off grid. Support j-boxes in hallway
Electrical Rough-In12/30/201312/30/201312/30/2013PPASS
DetailsDaryl DeGrange
ceiling cover 2nd floor Phone #: ###-#### >> Inspection requested via web by Karl Paige rough-in ok cover ceiling grid
Electrical Rough-In11/4/201311/4/201311/4/2013APASS
DetailsRock A. Hudson
Phone #: ###-#### >> Inspection requested via web by Karl Paige Basement and 2nd floor wall rough in ok cover