Final | 3/21/2014 | 3/24/2014 | 3/24/2014 | A | PASS |
Rock A. Hudson
|
|
|
Contact: Tom Hartung Phone #: ###-#### >> Inspection requested via web by Deb Gooden Final ok
|
Electrical Rough-In | 2/21/2014 | 2/24/2014 | 2/24/2014 | A | PASS |
Daryl DeGrange
|
|
|
Contact: Tom Hartung. ceiling inspection please Phone #: ###-#### >> Inspection requested via web by Deb Gooden correction done rough-in ok cover ceiling grid
|
Electrical Rough-In | 2/20/2014 | 2/20/2014 | 2/20/2014 | P | FAIL |
Daryl DeGrange
|
|
|
Contact: Tom Hartung. Ceiling inspection, ckt panel, etc. Phone #: ###-#### >> Inspection requested via web by Deb Gooden Remove luminaire whips from off ceiling grid, support j-box, install ko plugs as needed
|
Electrical Rough-In | 1/14/2014 | 1/15/2014 | 1/15/2014 | A | PASS |
Daryl DeGrange
|
|
|
Wall rough in inspection please. Contact name is Tom Hartung. Thank you. Phone #: ###-#### >> Inspection requested via web by Deb Gooden rough-in ok cover walls SERC rooms
|
Electrical Rough-In | 12/17/2013 | 12/17/2013 | 12/17/2013 | P | PASS |
Daryl DeGrange
|
|
|
Contact: Tom Hartung - scan room wall inspection please Phone #: ###-#### >> Inspection requested via web by Deb Gooden rough-in ok cover
|
Electrical Rough-In | 12/16/2013 | 12/16/2013 | 12/16/2013 | P | PASS |
Daryl DeGrange
|
|
|
Contact: Tom Hartung... wall re-inspection and feeder conduit inspection please Phone #: ###-#### >> Inspection requested via web by Deb Gooden Rough-in ok cover only that north of entry, east of hallway. Service feeder conduits ok
|
Electrical Rough-In | 12/13/2013 | 12/13/2013 | 12/13/2013 | P | FAIL |
Daryl DeGrange
|
|
|
Contact: Tom Hartung.. wall rough-in (partial) and feeder conduit inspections please Phone #: ###-#### >> Inspection requested via web by Deb Gooden NEC 330.12(1) AC cable subject to physical damage, Installed paralleled inside 2x4 steel studs
|
Conference | 12/3/2013 | 12/3/2013 | 12/3/2013 | P | DONE |
Daryl DeGrange
|
|
|
Contact- Tom Hartung Phone #: ###-#### >> Inspection requested via web by Deb Gooden Discussed with contractor floor penetrations, service outlet for rooftop equipment
|
Conference | 11/13/2013 | 11/13/2013 | 11/13/2013 | P | PASS |
Daryl DeGrange
|
|
|
Contact: Tom Hartung Phone #: ###-#### >> Inspection requested via web by Deb Gooden Discussed electrical requirements for pediatric locations
|