Final | 12/4/2014 | 12/5/2014 | 12/5/2014 | A | PASS |
Cevyn Recla
|
|
|
James Phone #: ###-#### Final ok
|
Electrical Rough-In | 9/19/2014 | 9/19/2014 | 9/19/2014 | P | PASS |
Rock A. Hudson
|
|
|
James Phone #: ###-#### West shed in back of house rough in ok cover
|
Rough-In Permanent Service | 9/9/2014 | 9/10/2014 | 9/10/2014 | A | FAIL |
Rock A. Hudson
|
|
|
James Tully Phone #: ###-#### Checked interior breaker for proper type and size. 314.16 Number of Conductors in Outlet, Device, and Junction Boxes, and Conduit Bodies. Boxes and conduit bodies shall be of an approved size to provide free space for all enclosed conductors. (1) Bored Holes. In both exposed and concealed locations, where a cable- or raceway-type wiring method is installed through bored holes in joists, rafters, or wood members, holes shall be bored so that the edge of the hole is not less than 32 mm (11/4 in.) from the nearest edge of the wood member. Where this distance cannot be maintained, the cable or raceway shall be protected from penetration by screws or nails by a steel plate(s) or bushing(s), at least 1.6 mm (1/16 in.) thick, and of appropriate length and width installed to cover the area of the wiring. All 15- and 20-ampere, 125- and 250-volt nonlocking-type receptacles shall be listed weather-resistant type. 406.12 Tamper-Resistant Receptacles. Tamper-resistant receptacles shall be installed as specified in 406.12(A) through (C). (A) Dwelling Units. In all areas specified in 210.52, all nonlocking-type 125-volt, 15- and 20-ampere receptacles shall be listed tamper-resistant receptacles
|
Conference | 11/22/2013 | 11/22/2013 | 11/22/2013 | P | DONE |
Daryl DeGrange
|
|
|
Please call 30min prior for access - James Phone #: ###-#### Discussed with homeowner electrical requirements detached portable shed, clearances from overhead service drop from hot tub. conductor size
|