Final | 3/9/2014 | 3/10/2014 | 3/10/2014 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Don Conley Final ok
|
Electrical Rough-In | 11/25/2013 | 11/25/2013 | 11/25/2013 | P | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Don Conley rough-in ok cover
|
Permanent Service | 11/24/2013 | 11/25/2013 | 11/25/2013 | A | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Don Conley p/s u/g n ok
|
Electrical Rough-In | 11/24/2013 | 11/25/2013 | 11/25/2013 | A | FAIL |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Don Conley NEC 334.30 NM cable shall be secured within 12in.of receptacle or light box. NEC 320.23 guard strips within 6 ft of attic access. Luminair boxes shall be supported from framing structure
|