Final | 3/6/2014 | 3/6/2014 | 3/6/2014 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by John VanZandt corrections made, ok final
|
Final | 3/4/2014 | 3/5/2014 | 3/5/2014 | A | FAIL |
Bob Reichert
|
|
|
Call for access Phone #: ###-#### >> Inspection requested via web by John VanZandt called, left correction notice, NEC 210.8(A) shall provide gfci for receptacles in garage and within 6' of sink, 250.94 shall install intersystem bond bar, 410.16(C) shall provide minimum 6" clearance from edge of closet shelf and edge of fluorescent luminaire
|
Electrical Rough-In | 12/5/2013 | 12/5/2013 | 12/5/2013 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by John VanZandt ri ok
|
Permanent Service | 12/5/2013 | 12/5/2013 | 12/5/2013 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by John VanZandt p/s u/g n ok
|