Final | 1/16/2014 | 1/16/2014 | 1/16/2014 | P | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by steve ragan final ok
|
Electrical Rough-In | 12/27/2013 | 12/27/2013 | 12/27/2013 | P | PASS |
Daryl DeGrange
|
|
|
Steve Phone #: ###-#### corrections done, rough-in ok cover
|
Electrical Rough-In | 12/23/2013 | 12/24/2013 | 12/24/2013 | A | FAIL |
Daryl DeGrange
|
|
|
Mark Phone #: ###-#### Commerial office Replace newly installed NM cable with MC cable. NEC 330.30 Secure MC cables within 12in.of box NEC 334.30 Secure NM cable wthin 12in. of box
|