Final | 1/18/2014 | 1/21/2014 | 1/21/2014 | A | PASS |
Daryl DeGrange
|
|
|
lock box code is 1359 Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack final ok
|
Electrical Rough-In | 1/18/2014 | 1/21/2014 | 1/21/2014 | A | PASS |
Daryl DeGrange
|
|
|
grid ceiling, lock box code is 1359 Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack rough-in ok cover ceiling grid
|
Electrical Rough-In | 12/23/2013 | 12/23/2013 | 12/23/2013 | A | PASS |
Daryl DeGrange
|
|
|
lock box code is 1359 Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack corrections done rough-in ok cover walls
|
Electrical Rough-In | 12/19/2013 | 12/20/2013 | 12/20/2013 | P | FAIL |
Daryl DeGrange
|
|
|
wall rough in Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack NEC 330.30(B) MC cable shall be secured within 12 in. of every box, cabnet, panel. Supported at intervals not to exceed 6 ft. NEC 362.30 ENT secured within 3 ft.
|