Final | 10/6/2014 | 10/7/2014 | 10/7/2014 | A | PASS |
Rock A. Hudson
|
|
|
Lockbox 4888. Thank you. Phone #: ###-#### Inspection requested via web by Clay Morgan Final ok
|
Final | 10/3/2014 | 10/3/2014 | 10/3/2014 | P | FAIL |
Rock A. Hudson
|
|
|
Lock box is 4888, thank you. Phone #: ###-#### Inspection requested via web by Clay Morgan Checked up interior, ok, open box on back fireplace on main level shall be safed off and covered. Seperate permit required for basement appartment as per notes from 7-24-14 inspection by Daryl DeGrange. 314.25 Covers and Canopies. In completed installations, each box shall have a cover, Checked up interior, ok, open box on back fireplace on main level shall be safed off and covered.
|
Rough-In Permanent Service | 7/23/2014 | 7/24/2014 | 7/24/2014 | A | PASS |
Daryl DeGrange
|
|
|
as per hold on parcel, this r.i. perm serv is for the business only. will need seperate address and permit for residential area-call Calvin for access into business ###-#### rough-in p/s o/h rec ok
|
Conference | 1/7/2014 | 1/7/2014 | 1/7/2014 | P | DONE |
Daryl DeGrange
|
|
|
Please call Jake when you are on your way. Thank You. Phone #: ###-#### >> Inspection requested via web by Clay Morgan Discussed with electrical contractor requirements for rewiring burn structure with residential and commerial use.
|