Final | 2/27/2014 | 2/27/2014 | 2/27/2014 | P | PASS |
Rock A. Hudson
|
|
|
Garage code 9045 Phone #: ###-#### >> Inspection requested via web by Neal Rumsey Final ok
|
Rough-In Permanent Service | 1/8/2014 | 1/9/2014 | 1/9/2014 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey ri ok, p/s u/g n ok
|
Rough-In Permanent Service | 1/8/2014 | 1/8/2014 | 1/8/2014 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey called, left correction notice, NEC 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing member, 314.20 boxes shall be flush with finished siding in combustible material, 314.23 shall protect nm cable within 6' of attic access, 334.30 shall secure nm cable within 12" of panel, BCC shall post address and job id sticker
|