Final | 5/7/2014 | 5/7/2014 | 5/7/2014 | A | PASS |
Rex Boyles
|
|
|
Final. Please call Rader at ###-#### 30 min prior to ensure access. Call me if there are any problems or questions. Thanks. Eric ###-#### Phone #: ###-#### >> Inspection requested via web by Eric Schroeder final ok
|
Permanent Service | 1/30/2014 | 1/31/2014 | 1/31/2014 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Eric Schroeder p/s o/h n ok
|
Electrical Rough-In | 1/31/2014 | 1/31/2014 | 1/31/2014 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Eric Schroeder Corrections done rough in ok cover
|
Electrical Rough-In | 1/29/2014 | 1/29/2014 | 1/29/2014 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Eric Schroeder called, left correction notice, NEC check main basement room function, NEC 210.52 shall add receptacles in 2' and 6' walls, 334.30 shall secure nm cale within 12" of panel and every 4 1/2',
|