Temporary Service | 1/24/2014 | 1/24/2014 | 1/24/2014 | P | PASS |
Daryl DeGrange
|
|
|
We replaced the 60 amp breaker and installed a 40 amp to feed the trailer... Phone #: ###-#### >> Inspection requested via web by Spencer McLean correction done, t/s o/h n ok
|
Temporary Service | 1/23/2014 | 1/23/2014 | 1/23/2014 | P | FAIL |
Daryl DeGrange
|
|
|
Temporary overhead power pole for job site. Phone #: ###-#### >> Inspection requested via web by Spencer McLean Power already connected prior to service inspection. NEC 400.5 Table 400.5(A) Column A #6 SOOW cord ampacity 45 ampere on 60 amp breaker. Secure cable to temp. pole were no strain relief connector is used.
|