Final | 2/27/2014 | 2/28/2014 | 2/28/2014 | A | PASS |
Rock A. Hudson
|
|
|
final inspection Phone #: ###-#### >> Inspection requested via web by Rowdy Monroe Final ok
|
Permanent Service | 1/29/2014 | 1/29/2014 | 1/29/2014 | P | PASS |
Rock A. Hudson
|
|
|
Service Only Phone #: ###-#### >> Inspection requested via web by Rowdy Monroe 42k AIC rated main confirmed. p/s u/g n ok
|
Rough-In Permanent Service | 1/22/2014 | 1/23/2014 | 1/23/2014 | A | FAIL |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Rowdy Monroe NEC 240.83 Interrupting rating of main breaker
|
Electrical Rough-In | 1/23/2014 | 1/23/2014 | 1/23/2014 | P | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Rowdy Monroe rough-in ok cover No permanent service without available AFC
|