Final | 5/8/2014 | 5/8/2014 | 5/8/2014 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Rhonda Zamagni ok final
|
Final | 5/7/2014 | 5/7/2014 | 5/7/2014 | P | FAIL |
Bob Reichert
|
|
|
Byron Phone #: ###-#### called, left correction notice, NEC 210.52 shall add receptacle in wall over 2', 406.4 receptacles shall be securely mounted, faceplates shall be flush, BCC 4-05-24 shall not cover wiring before inspection for ri, 4-05-26 all wiring shall be terminated at final
|
Permanent Service | 1/27/2014 | 1/28/2014 | 1/28/2014 | A | DONE |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Rhonda Zamagni sent thru 1/27/14
|
Electrical Rough-In | 1/27/2014 | 1/27/2014 | 1/27/2014 | P | PASS |
Bob Reichert
|
|
|
Re-inspect. Home is ready as soon as you can make it today, thank you. Phone #: ###-#### >> Inspection requested via web by Rhonda Zamagni ri ok
|
Permanent Service | 1/27/2014 | 1/27/2014 | 1/27/2014 | P | PASS |
Bob Reichert
|
|
|
Re-inspect. Home is ready as soon as you can make it today, thank you. Phone #: ###-#### >> Inspection requested via web by Rhonda Zamagni p/s u/g n ok
|
Electrical Rough-In | 1/24/2014 | 1/24/2014 | 1/24/2014 | P | FAIL |
Bob Reichert
|
|
|
Please call Byron for any questions Phone #: ###-#### >> Inspection requested via web by Rhonda Zamagni called recessed light boxes garage, 2' wall space requires outlet down stairs, upstairs 6' outlet space se bedroom, 1/1/4" nm behind furnace, told to post job id sticker
|