Permit Information
Permit NumberELE14-00212
StatusFinaled
Name SUBLIME ELECTRIC LLC
Site Address 4862 W ALAMOSA ST
Project Name 
Customer NumberAmy
ePlanReviewNo
Description
Electrical Permit - Alteration: Consult on rewire
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final12/10/201412/11/201412/11/2014PPASS
DetailsCevyn Recla
Please call the homeowner Amy ###-#### for access and please call Clay to meet you there ###-####. Thank You!!!! Phone #: ###-#### Inspection requested via web by Clay Morgan
corrections made, final OK
Final11/18/201411/18/201411/18/2014PFAIL
DetailsCevyn Recla
moved by Cevyn from AM inspection, per owner availability Spoke to Clay
BCC. 4.05.32 Code violattions are not to be retained

406.4.D-where means of ground exists, it shall be used, if not, an approved means of replacement receptacle to be used
210.8 outdoor receptacles to be GFI protected and weather resistant type
110.22 Disconnecting means shall be sufficeint durabililty- permanent label of panel
422.31 permanent disconnecting means of permanent appliances- lockout or disconnect of water heater
110.12 Mechanical execution of work, repair water heater wiring
210.8.A.7. GFI protection within 6 foot of sink
Final11/17/201411/18/201411/18/2014ACANC
DetailsCevyn Recla
Please call Amy 15 minutes ahead to meet ###-####. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan
called and moved to PM inspection
Conference11/5/201411/5/201411/5/2014PFAIL
DetailsRock A. Hudson
BCC 4-05-32- Code violations not to be retained.
NEC 322.56- Splices where made shall be in listed junction boxes.
NEC 394.12(5)- Concealed knob-and-tube wiring. Uses not permitted. (5) Hollow spaces of walls, ceilings, and attics where such spaces are insulated by loose, rolled, or foamed in place insulating material that envelops conductors.
* During kitchen repair open splices and concealed knob-and-tube wiring found buried in insulation in walls and ceilings. Due to fire hazard this wiring shall be replaced.
Electrical Rough-In2/18/20142/19/20142/19/2014APASS
DetailsRock A. Hudson
Please call homeowner Amy ###-#### when on your way, she will be gone from 10:30-11:00 but will be available any other time. Thank you. Phone #: ###-#### >> Inspection requested via web by Clay Morgan kitchen rough in ok for cover
Conference1/27/20141/28/20141/28/2014PDONE
DetailsRock A. Hudson
Please call Jake when you are on your way. Thank You. Phone #: ###-#### >> Inspection requested via web by Clay Morgan Discussed replacing knob and tube wiring found due to walls and ceiling being opened up because of flood on upper floor. 4-05-32- code violation not to be retaiined. Wiring in ceiling knob and tube to be replaced where exposed in kitchen area. Insurance company stated will not cover houses which have knob and tube wiring.