Final | 12/10/2014 | 12/11/2014 | 12/11/2014 | P | PASS |
Cevyn Recla
|
|
|
Please call the homeowner Amy ###-#### for access and please call Clay to meet you there ###-####. Thank You!!!! Phone #: ###-#### Inspection requested via web by Clay Morgan corrections made, final OK
|
Final | 11/18/2014 | 11/18/2014 | 11/18/2014 | P | FAIL |
Cevyn Recla
|
|
|
moved by Cevyn from AM inspection, per owner availability Spoke to Clay BCC. 4.05.32 Code violattions are not to be retained
406.4.D-where means of ground exists, it shall be used, if not, an approved means of replacement receptacle to be used 210.8 outdoor receptacles to be GFI protected and weather resistant type 110.22 Disconnecting means shall be sufficeint durabililty- permanent label of panel 422.31 permanent disconnecting means of permanent appliances- lockout or disconnect of water heater 110.12 Mechanical execution of work, repair water heater wiring 210.8.A.7. GFI protection within 6 foot of sink
|
Final | 11/17/2014 | 11/18/2014 | 11/18/2014 | A | CANC |
Cevyn Recla
|
|
|
Please call Amy 15 minutes ahead to meet ###-####. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan called and moved to PM inspection
|
Conference | 11/5/2014 | 11/5/2014 | 11/5/2014 | P | FAIL |
Rock A. Hudson
|
|
|
BCC 4-05-32- Code violations not to be retained. NEC 322.56- Splices where made shall be in listed junction boxes. NEC 394.12(5)- Concealed knob-and-tube wiring. Uses not permitted. (5) Hollow spaces of walls, ceilings, and attics where such spaces are insulated by loose, rolled, or foamed in place insulating material that envelops conductors. * During kitchen repair open splices and concealed knob-and-tube wiring found buried in insulation in walls and ceilings. Due to fire hazard this wiring shall be replaced.
|
Electrical Rough-In | 2/18/2014 | 2/19/2014 | 2/19/2014 | A | PASS |
Rock A. Hudson
|
|
|
Please call homeowner Amy ###-#### when on your way, she will be gone from 10:30-11:00 but will be available any other time. Thank you. Phone #: ###-#### >> Inspection requested via web by Clay Morgan kitchen rough in ok for cover
|
Conference | 1/27/2014 | 1/28/2014 | 1/28/2014 | P | DONE |
Rock A. Hudson
|
|
|
Please call Jake when you are on your way. Thank You. Phone #: ###-#### >> Inspection requested via web by Clay Morgan Discussed replacing knob and tube wiring found due to walls and ceiling being opened up because of flood on upper floor. 4-05-32- code violation not to be retaiined. Wiring in ceiling knob and tube to be replaced where exposed in kitchen area. Insurance company stated will not cover houses which have knob and tube wiring.
|