Final | 4/30/2014 | 5/1/2014 | 5/1/2014 | A | PASS |
Bob Reichert
|
|
|
inter system bonding added and MC cable supported Phone #: ###-#### >> Inspection requested via web by shane vigil ok final
|
Final | 4/28/2014 | 4/29/2014 | 4/29/2014 | A | FAIL |
Bob Reichert
|
|
|
home owner will let you in. basement game room and service final. Phone #: ###-#### >> Inspection requested via web by shane vigil called, shall not use a/c lines for mc support, shall add bond bar, will recall
|
Final | 2/25/2014 | 2/25/2014 | 2/25/2014 | P | CANC |
Rex Boyles
|
|
|
re energize service early pm please Phone #: ###-#### >> Inspection requested via web by shane vigil needed permenent service insp.
|
Permanent Service | 2/25/2014 | 2/25/2014 | 2/25/2014 | P | PASS |
Rex Boyles
|
|
|
re energize service early pm please Phone #: ###-#### >> Inspection requested via web by shane vigil p/s o/h rec ok
|
Electrical Rough-In | 2/12/2014 | 2/12/2014 | 2/12/2014 | P | PASS |
Rock A. Hudson
|
|
|
Heat unit xfmr reinspect Phone #: ###-#### >> Inspection requested via web by shane vigil Split system transformer and line volt flexible cord moved to interiior of wall unit. Rough in ok cover
|
Electrical Rough-In | 2/10/2014 | 2/11/2014 | 2/11/2014 | A | PART |
Rock A. Hudson
|
|
|
rough cover for new room, service to follow later. Phone #: ###-#### >> Inspection requested via web by shane vigil 400.8- Flexible cords shall not be ran through walls. Transformer shall be located in an accessible location. Wall to remain open under basement wall unit. Rest of walls ok cover
|