ELE-Aging Inspection | 5/23/2018 | 5/23/2018 | 5/23/2018 | | PASS |
Tom Saunders
|
|
|
final scheduled
|
Final | 5/23/2018 | 5/23/2018 | 5/23/2018 | A | PASS |
Tom Saunders
|
|
|
ok to final...no corrections needed
|
Final | 2/26/2014 | 2/26/2014 | 2/26/2014 | A | NR |
Daryl DeGrange
|
|
|
Try this one more time. Thank you Daryl.
Eric Phone #: ###-#### >> Inspection requested via web by Eric Schroeder Not ready for final at this time, power not connected yet
|
Permanent Service | 2/26/2014 | 2/26/2014 | 2/26/2014 | P | PASS |
Daryl DeGrange
|
|
|
Try this one more time. Thank you Daryl.
Eric Phone #: ###-#### >> Inspection requested via web by Eric Schroeder correction done p/s u/g rec ok
|
Final | 2/25/2014 | 2/25/2014 | 2/25/2014 | P | FAIL |
Daryl DeGrange
|
|
|
Inspection after ground rods have been installed. Phone #: ###-#### >> Inspection requested via web by Eric Schroeder NEC 312.5 Openings through which conductors enter shall be adequately closed. Number 4 grounding electrode conductor entering through 1in KO. All strands of electrode conductor shall terminate under one lug
|
Final | 2/24/2014 | 2/25/2014 | 2/25/2014 | A | CANC |
Daryl DeGrange
|
|
|
Inspection after repairs made. Call if there are any problems.
Thanks,
Eric Phone #: ###-#### >> Inspection requested via web by Eric Schroeder Inspection cancelled from web by: Eric Schroeder
|
Final | 2/21/2014 | 2/24/2014 | 2/24/2014 | P | CANC |
Daryl DeGrange
|
|
|
Final inspection after corrections made. Phone #: ###-#### >> Inspection requested via web by Eric Schroeder Inspection cancelled from web by: Eric Schroeder
|
Permanent Service | 2/11/2014 | 2/12/2014 | 2/12/2014 | A | FAIL |
Daryl DeGrange
|
|
|
Idaho Power Reconnect. The back slider door is unlocked. Or if there is a lock box on it the code is 7293 Phone #: ###-#### >> Inspection requested via web by Eric Schroeder NEC 110.26(A) working clearance for service meter. Clear vegetation near service meter NEC 250.56 Verify water pipe bond, provide 2-8ft grounding electrodes.
|
Permanent Service | 2/11/2014 | 2/12/2014 | 2/11/2014 | A | CANC |
Daryl DeGrange
|
|
|
Idaho Power Reconnect Phone #: ###-#### >> Inspection requested via web by Eric Schroeder Inspection cancelled from web by: Eric Schroeder
|