Final | 3/26/2014 | 3/27/2014 | 3/27/2014 | A | PASS |
Rock A. Hudson
|
|
|
reinspect Phone #: ###-#### >> Inspection requested via web by Barbara Szurgot Final ok
|
Final | 3/26/2014 | 3/26/2014 | 3/26/2014 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Barbara Szurgot 230.62- Energized live parts of service equiptment shall be enclosed. Install cover. 408.4- Service circuit dirctory shall be completed. 314.25- Box by water heater shall have cover 210.63- A 125 v, 15 or 20 amp receptical outlet shall be installed with in 25' of AC equiptment.
|
Electrical Rough-In | 3/6/2014 | 3/10/2014 | 3/10/2014 | A | PASS |
Rock A. Hudson
|
|
|
Rewire whole house. Phone #: ###-#### >> Inspection requested via web by Barbara Szurgot Rough in ok cover
|